DeltaChill™ Air Cooled and FreeCool
109
Chiller Technical Manual 7267818 V1.13.0_01_2018
Fre
eC
oo
l
ELECTRICAL DATA
10
11
12
Unit Data
DCF058DR-10DVV0
DCF062DR-10FVW0
DCF065DR-10FWW0
Nominal Run Amps
(1)
A
390.0
402.0
414.1
Maximum Start Amps
A
657.4
665.4
649.5
Recommended Mains Fuse Size
A
450
450
450
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (EC)
Quantity
10
10
10
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 55.2
55.2 / 59.2
59.2 / 59.2
Quantity
3 + 3
3 + 3
3 + 3
Motor Rating
kW
33.1 / 33.1
33.1 / 36.2
36.2 / 36.2
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
326 / 326
326 / 298
298 / 298
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
360.7
374.4
388.0
Reactive power reduction/saving
(4) kVAr
50.9
48.9
46.8
Maximum Start Amps
A
628.1
637.8
623.4
Recommended Mains Fuse Size
A
450
450
450
Electronic Soft-start
Nominal Run Amps
A
390.0
402.0
414.1
Maximum Start Amps
A
527.0
535.0
530.3
Recommended Mains Fuse
A
450
450
450
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
360.7
374.4
388.0
Maximum Start Amps
A
497.7
507.4
504.2
Recommended Mains Fuse Size
A
450.0
450.0
450.0
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
28.5
Unit Nominal Run Amps
A
411.1
423.1
442.5
Recommended Mains Fuse Size
A
450
450
500
Motor Rating
kW
12.1
12.1
16.4
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
35.0
Unit Nominal Run Amps
A
418.4
430.4
448.9
Recommended Mains Fuse Size
A
450
450
500
Motor Rating
kW
16.4
16.4
20.3
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
19.8
19.8
26.9
Unit Nominal Run Amps
A
405.7
417.9
435.8
Recommended Mains Fuse Size
A
450
450
500
Motor Rating
kW
12.4
12.4
16.8
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
33.2
Unit Nominal Run Amps
A
411.4
423.6
440.9
Recommended Mains Fuse Size
A
450
450
500
Motor Rating
kW
16.8
16.8
20.7
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data - Regular Quiet