![AIREDALE DeltaChill Technical Manual Download Page 187](http://html.mh-extra.com/html/airedale/deltachill/deltachill_technical-manual_2876547187.webp)
Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
187
Chiller Technical Manual 7267818 V1.13.0_01_2018
A
ir C
oo
led
101
102
103
Unit Data
DCC051DR-10EYY0
DCC052DR-09DYV0
DCC056DR-10DVV0
Nominal Run Amps
(1)
A
341.1
361.5
390.0
Maximum Start Amps
A
616.7
628.9
657.4
Recommended Mains Fuse Size
A
355
400
450
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (EC)
Quantity
10
9
10
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
47.9 / 47.9
47.9 / 55.2
55.2 / 55.2
Quantity
3 + 3
3 + 3
3 + 3
Motor Rating
kW
29.8 / 29.8
29.8 / 33.1
33.1 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
326 / 326
326 / 326
326 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
326.1
339.5
360.7
Reactive power reduction/saving
(4)
kVAr
28.5
39.7
50.9
Maximum Start Amps
A
601.7
606.9
628.1
Recommended Mains Fuse Size
A
355
400
450
Electronic Soft-start
Nominal Run Amps
A
341.1
361.5
390.0
Maximum Start Amps
A
486.3
498.5
527.0
Recommended Mains Fuse
A
355
400
450
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
326.1
339.5
360.7
Maximum Start Amps
A
471.3
476.5
497.7
Recommended Mains Fuse Size
A
355
400
450
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
8.9
8.9
8.9
Unit Nominal Run Amps
A
349.5
370.0
398.5
Recommended Mains Fuse Size
A
400
400
450
Motor Rating
kW
4.4
4.4
4.4
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
11.2
Unit Nominal Run Amps
A
352.1
372.5
401.0
Recommended Mains Fuse Size
A
400
400
450
Motor Rating
kW
6.1
6.1
6.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
7.3
7.3
7.3
Unit Nominal Run Amps
A
347.1
367.3
395.7
Recommended Mains Fuse Size
A
400
400
450
Motor Rating
kW
4.5
4.5
4.5
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
10.1
10.1
10.1
Unit Nominal Run Amps
A
349.4
369.6
398.0
Recommended Mains Fuse Size
A
400
400
450
Motor Rating
kW
6.3
6.3
6.3
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold
DCC Electrical Data - Regular Quiet