DeltaChill™ Air Cooled and FreeCool
73
Chiller Technical Manual 7267818 V1.13.0_01_2018
Fre
eC
oo
l
1
2
3
DCF046DR-07DXY0
DCF048DR-07DPY0
DCF051DR-08DPV0
FreeCooling
Yes
Yes
Yes
Enhance Capital Allowance
No
No
No
Number of Refrigeration Circuits
2
2
2
Cooling Duty - EC Fans
Nominal Output - Mechanical
(1) kW
466.8
481.9
509.1
Nominal Input - Mechanical
kW
170.0
175.5
178.7
EER
(2)
2.75
2.75
2.85
ESEER
3.80
3.67
3.71
Nominal Output - Free Cooling
kW
345.6
348.7
389.9
Ambient temperature for
100% Free Cooling
(5) °C
-1.3
-1.6
-0.7
Capacity Steps
%
15-35-50-70-85-100
25-45-65-85-100
25-45-65-80-100
Minimum Turndown Ratio
0.16
0.24
0.23
Dimensions (H x W x L)
mm
2682 x 2200 x 4846
2682 x 2200 x 4846
2682 x 2200 x 4846
Weight
Machine
(3) kg
4465
4345
4450
Operating
kg
5060
4940
5065
Water Volume (Total Internal)
l
595
595
615
Maximum Waterflow
l/s
35.1
35.1
35.1
Minimum Waterflow
l/s
8.0
13.4
13.4
Face Area (Total)
m²
2.38
2.38
2.38
Nominal Airflow - EC Fans
m³/s
41.1
41.1
47.0
Quantity
7
7
8
Maximum Speed - EC Fans
rpm
1026
1026
1026
Compressor
Trio + Trio
Trio
Trio
Quantity of Compressors
6
5
5
Oil Charge Volume (Total)
l
3 x 5.3 + 3 x 5.3
2 x 5.3 + 3 x 5.3
2 x 5.3 + 3 x 5.3
Refrigeration
R410A / 2088
Charge (Total)
kg
24 + 30
24 + 31
24 + 34
GWP Tonnes Equivalent CO
2
tCO2
50 + 63
50 + 65
50 + 71
Refrigerant Control
Electronic Expansion Valve (EEV)
Water Inlet / Outlet - Unit
DN125
DN125
DN125
Water Drain / Bleed - Evap
inch
1/2
1/2
1/2
Water System
Minimum System Water Volume
(4)
l
1371
2149
2149
Maximum System
Operating Pressure
Bar
10
10
10
DCF Mechanical Data - Regular Quiet
(1)
Based on units performance at 15/10°C return/supply temperatures, 35°C ambient, 20% Ethylene Glycol.
All performance data supplied in accordance with BBS EN14511-1:2013
(2)
EER = DX Cooling Output / (Compressor input power + Fan Input Power),
(3)
Based on standard unit without options, operating weight includes refrigerant charge and water volume.
For unit weights with waterside options fitted please refer to Airedale.
(4)
For minimum system volume, refer to Design Features & Information - Minimum System Water Volume Calculations
(5)
Ambient temperature that full Freecool capacity can be achieved