Chillers
DeltaChill™ Air Cooled and FreeCool
122
Chiller Technical Manual 7267818 V1.13.0_01_2018
Te
ch
ni
ca
l
Fr
ee
C
oo
l
ELECTRICAL DATA
49
50
51
Unit Data
DCF098TR-21HVVW
DCF101TR-21HVWW
DCF103TR-21HWWW
Nominal Run Amps
(1)
A
620.1
632.2
644.4
Maximum Start Amps
A
883.5
895.6
879.8
Recommended Mains Fuse Size
A
670
670
670
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (EC)
Quantity
21
21
21
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 55.2 / 59.2
55.2 / 59.2 / 59.2
59.2 / 59.2 / 59.2
Quantity
3 + 3 + 3
3 + 3 + 3
3 + 3 + 3
Motor Rating
kW
33.1 / 33.1 / 36.2
33.1 / 36.2 / 36.2
36.2 / 36.2 / 36.2
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
326 / 326 / 298
326 / 298 / 298
298 / 298 / 298
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
578.0
591.7
605.4
Reactive power reduction/saving
(4) kVAr
74.5
72.4
70.3
Maximum Start Amps
A
841.4
855.1
840.8
Recommended Mains Fuse Size
A
670
670
670
Electronic Soft-start
Nominal Run Amps
A
620.1
632.2
644.4
Maximum Start Amps
A
753.1
765.2
760.6
Recommended Mains Fuse
A
670
670
670
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
578.0
591.7
605.4
Maximum Start Amps
A
711.0
724.7
721.6
Recommended Mains Fuse Size
A
670.0
670.0
670.0
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
28.5
35.0
35.0
Unit Nominal Run Amps
A
648.4
667.0
679.1
Recommended Mains Fuse Size
A
670
710
710
Motor Rating
kW
16.4
20.3
20.3
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
35.0
41.5
41.5
Unit Nominal Run Amps
A
654.9
673.5
685.6
Recommended Mains Fuse Size
A
710
710
710
Motor Rating
kW
20.3
23.9
23.9
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
26.9
33.2
33.2
Unit Nominal Run Amps
A
641.6
658.9
671.2
Recommended Mains Fuse Size
A
670
710
710
Motor Rating
kW
16.8
20.7
20.7
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
33.2
39.2
39.2
Unit Nominal Run Amps
A
646.7
663.7
676.0
Recommended Mains Fuse Size
A
710
710
710
Motor Rating
kW
20.7
24.4
24.4
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.