Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
155
Chiller Technical Manual 7267818 V1.13.0_01_2018
A
ir C
oo
led
Ambient (°C)
Model
Supply
Temp
°C
25°C
30°C
35°C
40°C
Output
Input
Output
Input
Output
Input
Output
Input
kW
kW
kW
kW
kW
kW
kW
kW
176
DCC080TX-19GYYV
5
832.1
211.2
788.3
232.9
740.2
257.6
688.1
285.4
6
856.5
212.7
811.5
234.3
762.1
259.1
708.5
286.9
7
881.2
214.1
835.1
235.8
784.3
260.6
729.2
288.4
8
906.2
215.6
859.0
237.4
806.8
262.2
750.3
290.0
9
931.5
217.2
883.1
238.9
829.7
263.8
771.7
291.6
10
957.1
218.8
907.5
240.5
852.7
265.4
793.3
293.3
177
DCC081TX-22GYYV
5
845.5
206.6
803.1
227.6
755.9
251.6
704.5
278.7
6
870.7
207.9
827.2
228.8
778.6
252.9
725.8
280.0
7
896.3
209.2
851.5
230.1
801.7
254.2
747.4
281.3
8
922.2
210.5
876.2
231.5
825.1
255.5
769.3
282.7
9
948.3
211.9
901.1
232.9
848.8
256.9
791.6
284.1
10
974.6
213.4
926.4
234.3
872.8
258.4
814.2
285.5
178
DCC082TX-20GYVV
5
853.2
213.9
808.6
236.0
759.4
261.4
706.0
290.0
6
878.4
215.3
832.6
237.5
782.1
262.8
727.1
291.5
7
903.9
216.8
856.9
238.9
805.0
264.3
748.5
293.0
8
929.6
218.3
881.5
240.4
828.3
265.9
770.3
294.5
9
955.6
219.8
906.4
242.0
851.8
267.4
792.4
296.1
10
981.9
221.4
931.5
243.6
875.7
269.1
814.8
297.7
179
DCC085TX-21GVVV
5
874.4
216.7
828.9
239.2
778.7
265.2
723.9
294.6
6
900.3
218.0
853.7
240.6
802.0
266.6
745.7
296.0
7
926.5
219.4
878.7
242.0
825.7
268.1
767.9
297.5
8
953.0
220.9
904.1
243.5
849.7
269.6
790.4
299.0
9
979.8
222.4
929.7
245.0
874.0
271.1
813.2
300.6
10
1006.7
224.0
955.6
246.6
898.6
272.7
836.3
302.2
180
DCC088TX-21GVVW
5
914.3
228.5
865.5
252.2
811.9
279.5
753.9
310.2
6
941.4
230.1
891.3
253.8
836.2
281.1
776.4
311.8
7
968.8
231.7
917.4
255.4
860.8
282.7
799.3
313.5
8
996.5
233.3
943.8
257.1
885.7
284.4
822.6
315.2
9
1024.5
235.0
970.1
258.8
910.9
286.1
846.2
317.0
10
1052.8
236.7
997.5
260.5
936.5
287.9
870.2
318.8
181
DCC091TX-21GVWW
5
945.2
239.9
894.6
264.8
839.0
293.4
778.8
325.5
6
972.7
241.6
920.8
266.5
863.7
295.1
801.8
327.3
7
1000.6
243.3
947.3
268.3
888.7
296.9
825.1
329.1
8
1028.8
245.0
974.2
270.0
914.0
298.7
848.7
331.0
9
1057.3
246.9
1000.6
272.0
939.6
300.6
872.7
332.9
10
1086.0
248.7
1028.8
273.8
965.6
302.5
897.0
334.9
182
DCC094TX-21GWWW
5
976.0
251.3
923.6
277.4
866.1
307.3
803.8
340.8
6
1004.1
253.1
950.3
279.2
891.2
309.1
827.1
342.8
7
1032.5
254.9
977.3
281.1
916.6
311.1
850.8
344.8
8
1061.2
256.8
1004.6
283.0
942.3
313.0
874.8
346.8
9
1090.1
258.7
1031.1
285.2
968.4
315.1
899.2
348.8
10
1119.2
260.7
1060.0
287.0
994.7
317.1
923.9
351.0
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (comp fans).
3
Duties applicable for chilled water ∆T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x ∆T)
6
For conditions outside of those quoted please refer to Airedale.
DCC Performance Data EC Fans