Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
131
Chiller Technical Manual 7267818 V1.13.0_01_2018
Fre
eC
oo
l
ELECTRICAL DATA
76
77
78
Unit Data
DCF066DX-16FVW0
DCF069DX-16FWW0
DCF073TX-16GPPY
Nominal Run Amps
(1)
A
425.1
437.3
463.3
Maximum Start Amps
A
688.5
672.7
726.7
Recommended Mains Fuse Size
A
450
500
500
Evaporator
Immersion Heater Rating
W
170
170
250
Condenser Fan - Per Fan (EC)
Quantity
16
16
16
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 59.2
59.2 / 59.2
59.2 / 59.2 / 47.9
Quantity
3 + 3
3 + 3
2 + 2 + 3
Motor Rating
kW
33.1 / 36.2
36.2 / 36.2
36.2 / 36.2 / 29.8
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
326 / 298
298 / 298
298 / 298 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
397.7
411.4
438.6
Reactive power reduction/saving
(4) kVAr
49.0
46.9
45.6
Maximum Start Amps
A
661.1
646.8
702.0
Recommended Mains Fuse Size
A
450
500
500
Electronic Soft-start
Nominal Run Amps
A
425.1
437.3
463.3
Maximum Start Amps
A
558.1
553.5
596.3
Recommended Mains Fuse
A
450
500
500
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
397.7
411.4
438.6
Maximum Start Amps
A
530.7
527.6
571.6
Recommended Mains Fuse Size
A
450
500
500
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
21.2
Unit Nominal Run Amps
A
446.2
458.3
484.3
Recommended Mains Fuse Size
A
500
500
560
Motor Rating
kW
12.1
12.1
12.1
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
28.5
Unit Nominal Run Amps
A
453.5
465.6
491.6
Recommended Mains Fuse Size
A
500
500
560
Motor Rating
kW
16.4
16.4
16.4
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
19.8
19.8
19.8
Unit Nominal Run Amps
A
441.1
453.3
479.5
Recommended Mains Fuse Size
A
500
500
500
Motor Rating
kW
12.4
12.4
12.4
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
26.9
Unit Nominal Run Amps
A
446.8
459.1
485.2
Recommended Mains Fuse Size
A
500
500
560
Motor Rating
kW
16.8
16.8
16.8
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data Extra Quiet