Notes: Units DCF047DX-09DXY0 DCF049DX-09DPY0 DCF051DX-10DPV0
SEPR
1,3,5
6.33
6.08
6.15
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
506689
542581
565609
Rated Refrigerant Capacity
P
A
1,3,5 kW
433
445.6
469.7
Rated Power Input D
A
kW
163.4
169.4
172.7
Rated EER
DC,A
2.65
2.63
2.72
Declared Refrigerant Capacity P
B
1,3,5 kW
411.1 / 346.3
426.8 / 331.5
442.0 / 338.6
Declared Power Input D
B
kW
106.7 / 85.5
111.5 / 86.1
113.6 / 87.4
Declared EER
DC,B
3.85 / 4.05
3.83 / 3.85
3.89 / 3.88
Declared Refrigerant Capacity P
C
1,3,5 kW
376.7 / 274.4
469.1 / 365.6
485.0 / 373.3
Declared Power Input D
C
kW
71.6 / 50.3
93.6 / 72.2
95.1 / 73.2
Declared EER
DC,C
5.26 / 5.45
5.01 / 5.06
5.10 / 5.10
Declared Refrigerant Capacity P
D
1,3,5 kW
343.7 / 287.8
353.2 / 253.6
372.3 / 260.8
Declared Power Input D
D
kW
35.2 / 43.6
38.3 / 39.0
40.0 / 40.3
Declared EER
DC,D
9.76 / 6.61
9.23 / 6.50
9.31 / 6.48
SSCEE
2,3,5
%
161.0
152.3
153.3
SSCEE Tier
6
Tier 1 (2018)
Not Compliant
Not Compliant
Rated Cooling Capacity P
rated,c
2,4,5
435.7
448.8
n/a
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
433
445.6
n/a
Declared EER
d
35°C
2.65
2.63
n/a
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
411.1 / 346.3
426.8 / 331.5
n/a
Declared EER
d
30°C
3.85 / 4.05
3.83 / 3.85
n/a
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
376.7 / 274.4
469.1 / 365.6
n/a
Declared EER
d
25°C
5.26 / 5.45
5.01 / 5.06
n/a
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
343.7 / 287.8
353.2 / 253.6
n/a
Declared EER
d
20°C
9.76 / 6.61
9.23 / 6.50
n/a
Sound Power Level LWA
dB(A)
n/a
Air flow rate
m³/h
129520
129520
n/a
Off mode P
OFF
kW
0.157
0.157
n/a
Thermostat-off mode P
TO
kW
3.025
3.595
n/a
Standby Mode P
SB
kW
0.276
0.264
n/a
Crankcase heater mode P
CK
kW
0.000
0.000
n/a
Technical Data
Ecodesign
DCF047DX-09DXY0, DCF049DX-09DPY0, DCF051DX-10DPV0
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections
Chillers
Introduction
DeltaChill™ Air Cooled and FreeCool
284
Chiller Technical Manual 7267818 V1.13.0_01_2018
Te
ch
ni
ca
l