Chillers
DeltaChill™Air Cooled and FreeCool
33
Chiller Technical Manual 7267818 V1.13.0_01_2018
Installation Data
Weights, Point Loadings & Centre of Gravity (C of G) DCC
Point loads
L1
L2
L3
L4
L5
L6
L7
R1
R2
R3
R4
R5
R6
R7
C of
G 1
C of
G 2
kg
mm mm
98 DCC047DR-08EPV0
500 565 615
685 775 850
935 2460
99 DCC049DR-08EYY0
525 565 600
750 810 855
915 2385
100 DCC049DR-10EPV0
525 505 485 465
710 680 660 630
940 2695
101 DCC051DR-10EYY0
530 505 490 470
720 690 665 635
940 2690
102 DCC052DR-09DYV0
530 510 490 470
730 700 675 650
935 2695
103 DCC056DR-10DVV0
535 510 490 470
745 715 685 655
925 2680
104 DCC058DR-10DVW0
560 575 590 610
725 750 770 790
960 2945
105 DCC061DR-10DWW0 635 635 640 640
865 870 870 875
935 3420
106 DCC065TR-10GPPY
670 655 645 630
935 920 900 875
925 3310
107 DCC050DR-12EPV0
620 595 570 595 525
820 785 750 785 690
955 3660
108 DCC052DR-12EYY0
625 600 575 600 530
825 795 760 795 700
955 3670
109 DCC054DR-11DYV0
700 650 595 650 520
920 850 780 850 680
960 4020
110 DCC058DR-12DVV0
700 650 600 650 520
930 865 790 865 690
955 4025
111 DCC060DR-12DVW0
705 655 600 655 525
940 875 800 875 700
950 4020
112 DCC063DR-12DWW0 710 655 600 655 520
955 885 810 885 700
945 4005
113 DCC069TR-11GPYY
495 485 480 470
660 645 635 625
955 2775
114 DCC074TR-12GYYY
515 495 480 460
710 680 660 630
935 2695
115 DCC056DR-13DYV0
600 580 560 535
785 760 730 700
960 3230
116 DCC059DR-14DVV0
610 585 560 530
800 770 735 695
955 3190
117 DCC061DR-14DVW0
610 585 560 530
815 780 745 705
950 3195
118 DCC065DR-14DWW0 615 590 560 530
830 795 755 715
945 3175
119 DCC068TR-13GPPY
590 570 555 570 525
750 730 705 730 670
975 3770
120 DCC072TR-14GPYY
595 580 565 580 535
780 760 735 760 695
960 3770
121 DCC077TR-13GYYV
700 650 595 650 520
915 850 780 850 680
960 4030
122 DCC080TR-14GYVV
710 660 600 660 520
925 860 785 860 680
960 4000
123 DCC070TR-16GPPY
745 690 635 690 535
965 895 825 895 695
965 4345
124 DCC077TR-15GYYY
755 700 640 700 535
975 905 830 905 695
965 4310
(1) Point load numbering starts from the control panel end of the chiller. Illustration above is for a 8 mount configuration
(2) Point loads indicated are for standard unit only
2
1
L1
L2
L3
L4
R1
R2
R3
R4
= C of G