Chillers
DeltaChill™ Air Cooled and FreeCool
108
Chiller Technical Manual 7267818 V1.13.0_01_2018
Te
ch
ni
ca
l
Fr
ee
C
oo
l
ELECTRICAL DATA
7
8
9
Unit Data
DCF053DR-10DPV0
DCF055DR-09DYV0
DCF055DR-10DYY0
Nominal Run Amps
(1)
A
339.4
361.5
341.1
Maximum Start Amps
A
602.8
628.9
616.7
Recommended Mains Fuse Size
A
400
400
355
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (EC)
Quantity
10
9
10
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
59.2 / 55.2
47.9 / 55.2
47.9 / 47.9
Quantity
2 + 3
3 + 3
3 + 3
Motor Rating
kW
36.2 / 33.1
29.8 / 33.1
29.8 / 29.8
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
298 / 326
326 / 326
326 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
316.2
339.5
326.1
Reactive power reduction/saving
(4) kVAr
41.1
39.7
28.5
Maximum Start Amps
A
579.6
606.9
601.7
Recommended Mains Fuse Size
A
400
400
355
Electronic Soft-start
Nominal Run Amps
A
339.4
361.5
341.1
Maximum Start Amps
A
472.4
498.5
486.3
Recommended Mains Fuse
A
400
400
355
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
316.2
339.5
326.1
Maximum Start Amps
A
449.2
476.5
471.3
Recommended Mains Fuse Size
A
400.0
400.0
355.0
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
21.2
Unit Nominal Run Amps
A
360.5
382.5
362.1
Recommended Mains Fuse Size
A
400
400
400
Motor Rating
kW
12.1
12.1
12.1
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
28.5
Unit Nominal Run Amps
A
367.8
389.8
369.3
Recommended Mains Fuse Size
A
400
450
400
Motor Rating
kW
16.4
16.4
16.4
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
19.8
19.8
19.8
Unit Nominal Run Amps
A
355.3
377.5
357.4
Recommended Mains Fuse Size
A
400
400
400
Motor Rating
kW
12.4
12.4
12.4
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
26.9
Unit Nominal Run Amps
A
361.0
383.3
363.3
Recommended Mains Fuse Size
A
400
450
400
Motor Rating
kW
16.8
16.8
16.8
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data - Regular Quiet