Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
153
Chiller Technical Manual 7267818 V1.13.0_01_2018
A
ir C
oo
led
Ambient (°C)
Model
Supply
Temp
°C
25°C
30°C
35°C
40°C
Output
Input
Output
Input
Output
Input
Output
Input
kW
kW
kW
kW
kW
kW
kW
kW
162
DCC065DX-16DWW0
5
670.4
164.2
635.6
181.1
597.3
200.4
555.7
222.2
6
689.8
165.3
654.1
182.1
614.8
201.5
572.0
223.4
7
709.3
166.4
672.8
183.3
632.5
202.6
588.6
224.5
8
729.1
167.6
691.8
184.4
650.4
203.8
605.4
225.7
9
749.1
168.7
710.9
185.6
668.6
205.0
622.5
226.9
10
769.2
169.9
730.2
186.8
686.9
206.2
639.7
228.2
163
DCC068TX-16GPPY
5
714.8
180.2
676.8
198.6
635.1
219.7
590.1
243.4
6
735.6
181.4
696.6
199.9
653.7
221.0
607.4
244.7
7
756.6
182.7
716.5
201.2
672.6
222.3
625.0
246.1
8
777.9
184.0
736.8
202.5
691.7
223.7
642.8
247.5
9
799.3
185.4
757.3
203.9
711.0
225.1
660.9
248.9
10
821.0
186.8
777.9
205.3
730.6
226.5
679.3
250.4
164
DCC075TX-15GYYY
5
790.1
216.6
745.9
238.8
697.8
263.9
646.2
291.7
6
812.7
218.3
767.3
240.6
717.8
265.7
664.6
293.5
7
835.6
220.0
788.9
242.4
738.0
267.5
683.4
295.4
8
858.8
221.8
810.8
244.2
758.5
269.4
702.4
297.3
9
882.2
223.6
832.9
246.1
779.3
271.4
721.7
299.3
10
905.8
225.5
855.2
248.0
800.3
273.3
741.3
301.3
165
DCC077TX-16GYYV
5
812.6
218.6
767.6
241.3
718.4
267.0
665.4
295.6
6
836.1
220.3
789.8
243.0
739.2
268.7
684.6
297.4
7
859.8
222.0
812.2
244.8
760.2
270.5
704.2
299.2
8
883.7
223.7
834.9
246.6
781.5
272.4
724.0
301.1
9
907.9
225.5
857.9
248.4
803.1
274.3
744.1
303.0
10
932.4
227.4
881.1
250.3
825.0
276.2
764.5
305.0
166
DCC072TX-17GPYY
5
752.2
193.7
712.9
213.6
669.7
236.2
622.9
261.5
6
774.0
195.0
733.7
214.9
689.3
237.6
641.2
262.9
7
796.0
196.4
754.7
216.3
709.1
239.0
659.7
264.4
8
818.3
197.7
776.0
217.7
729.2
240.4
678.5
265.9
9
840.8
199.2
797.5
219.1
749.6
241.9
697.6
267.4
10
863.5
200.6
819.2
220.6
770.2
243.4
716.9
268.9
167
DCC077TX-18GYYY
5
810.9
208.5
768.0
229.7
721.0
253.8
670.2
280.8
6
834.6
210.0
790.5
231.2
742.2
255.3
689.9
282.3
7
858.6
211.5
813.3
232.7
763.6
256.9
709.9
283.9
8
882.9
213.0
836.4
234.3
785.4
258.5
730.3
285.5
9
907.4
214.5
859.8
235.9
807.5
260.1
750.9
287.2
10
932.2
216.1
883.4
237.5
829.8
261.8
771.9
288.8
168
DCC080TX-17GYVV
5
835.1
220.7
789.3
243.8
739.0
270.1
684.7
299.5
6
859.4
222.3
812.3
245.4
760.6
271.8
704.7
301.3
7
883.9
224.0
835.6
247.1
782.4
273.5
725.0
303.0
8
908.7
225.7
859.1
248.9
804.6
275.3
745.6
304.9
9
933.7
227.4
882.9
250.7
827.0
277.2
766.5
306.7
10
959.0
229.3
906.9
252.6
849.7
279.1
787.7
308.7
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (comp fans).
3
Duties applicable for chilled water ∆T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x ∆T)
6
For conditions outside of those quoted please refer to Airedale.
DCC Performance Data EC Fans