ELECTRICAL DATA
161
162
163
Unit Data
DCC061DX-16DVW0
DCC065DX-16DWW0
DCC068TX-16GPPY
Nominal Run Amps
(1)
A
425.1
437.3
463.3
Maximum Start Amps
A
688.5
672.7
726.7
Recommended Mains Fuse Size
A
450
500
500
Evaporator
Immersion Heater Rating
W
170
170
250
Condenser Fan - Per Fan (EC)
Quantity
16
16
16
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 59.2
59.2 / 59.2
59.2 / 59.2 / 47.9
Quantity
3 + 3
3 + 3
2 + 2 + 3
Motor Rating
kW
33.1 / 36.2
36.2 / 36.2
36.2 / 36.2 / 29.8
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
326 / 298
298 / 298
298 / 298 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
397.7
411.4
438.6
Reactive power reduction/saving
(4)
kVAr
49.0
46.9
45.6
Maximum Start Amps
A
661.1
646.8
702.0
Recommended Mains Fuse Size
A
450
500
500
Electronic Soft-start
Nominal Run Amps
A
425.1
437.3
463.3
Maximum Start Amps
A
558.1
553.5
596.3
Recommended Mains Fuse
A
450
500
500
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
397.7
411.4
438.6
Maximum Start Amps
A
530.7
527.6
571.6
Recommended Mains Fuse Size
A
450
500
500
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
11.2
Unit Nominal Run Amps
A
436.2
448.3
474.3
Recommended Mains Fuse Size
A
500
500
500
Motor Rating
kW
6.2
6.2
6.2
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
14.8
14.8
21.2
Unit Nominal Run Amps
A
439.8
451.9
484.3
Recommended Mains Fuse Size
A
500
500
560
Motor Rating
kW
8.4
8.4
12.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
10.2
10.2
10.2
Unit Nominal Run Amps
A
433.3
445.5
471.6
Recommended Mains Fuse Size
A
500
500
500
Motor Rating
kW
6.4
6.4
6.4
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
13.9
13.9
19.8
Unit Nominal Run Amps
A
436.3
448.5
479.5
Recommended Mains Fuse Size
A
500
500
500
Motor Rating
kW
8.6
8.6
12.4
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold
DCC Electrical Data - Extra Quiet