Chillers
DeltaChill™ Air Cooled and FreeCool
114
Chiller Technical Manual 7267818 V1.13.0_01_2018
Te
ch
ni
ca
l
Fr
ee
C
oo
l
ELECTRICAL DATA
25
26
27
Unit Data
DCF062DR-14DVV0
DCF066DR-14FVW0
DCF070DR-14FWW0
Nominal Run Amps
(1)
A
405.3
417.4
429.6
Maximum Start Amps
A
672.7
680.8
665.0
Recommended Mains Fuse Size
A
450
450
450
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (EC)
Quantity
14
14
14
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 55.2
55.2 / 59.2
59.2 / 59.2
Quantity
3 + 3
3 + 3
3 + 3
Motor Rating
kW
33.1 / 33.1
33.1 / 36.2
36.2 / 36.2
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
326 / 326
326 / 298
298 / 298
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
376.3
389.9
403.6
Reactive power reduction/saving
(4) kVAr
51.0
49.0
46.9
Maximum Start Amps
A
643.7
653.3
639.0
Recommended Mains Fuse Size
A
450
450
450
Electronic Soft-start
Nominal Run Amps
A
405.3
417.4
429.6
Maximum Start Amps
A
542.3
550.4
545.8
Recommended Mains Fuse
A
450
450
450
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
376.3
389.9
403.6
Maximum Start Amps
A
513.3
522.9
519.8
Recommended Mains Fuse Size
A
450.0
450.0
450.0
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
21.2
Unit Nominal Run Amps
A
426.4
438.5
450.6
Recommended Mains Fuse Size
A
450
500
500
Motor Rating
kW
12.1
12.1
12.1
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
28.5
Unit Nominal Run Amps
A
433.7
445.8
457.9
Recommended Mains Fuse Size
A
450
500
500
Motor Rating
kW
16.4
16.4
16.4
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
19.8
19.8
19.8
Unit Nominal Run Amps
A
421.2
433.4
445.6
Recommended Mains Fuse Size
A
450
500
500
Motor Rating
kW
12.4
12.4
12.4
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
26.9
Unit Nominal Run Amps
A
426.9
439.1
451.3
Recommended Mains Fuse Size
A
450
500
500
Motor Rating
kW
16.8
16.8
16.8
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data - Regular Quiet