background image

RLC-SVU007D-GB

Tracer™ TD7 with UC 800

User Guide

Original instructions

Summary of Contents for Tracer TD7

Page 1: ...RLC SVU007D GB Tracer TD7 with UC 800 User Guide Original instructions ...

Page 2: ... 754 1333 x 864 1333 x 1008 1333 1133 Height mm 260 310 360 460 660 Weight kg 32 46 61 76 118 Colour galvanised steel Recommended fuse size Unit alone aM gI A 8 16 8 16 8 16 8 25 8 25 Unit with electric heater gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 25 1 Conditions Water entering leaving temperature 7 12 C Air inlet temperature 27 19 C DB WB Nominal air flow 2 Conditions Water entering le...

Page 3: ... storing component provided by Trane or others refer to the appropriate manufacturer s literature for allowable waiting periods for discharge of capacitors Verify with an appropriate voltmeter that all capacitors have discharged DC bus capacitors retain hazardous voltages after input power has been disconnected Follow proper lockout tagout procedures to ensure the power cannot be inadvertently ene...

Page 4: ...r temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bars Installer Supplied Components InterconnectingWiring Installer Supplied Components Customer wiring interface connections are shown in the electrical schematics and connection diagrams that are shipped with the unit The installer must provide the following components if not ordered with the unit Power supply wiring in co...

Page 5: ... 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 Installer Supplied Components InterconnectingWiring If water flow is not established in 20 minutes for normal transition the UC800 de energizes ...

Page 6: ... The relay will be energized when the event state occurs Table 3 Chiller event status descriptions Alarm Latching This output is true whenever there is any active latching shutdown diagnostic that targets the Unit Circuit or any of the Compressors on a circuit Alarm NonLatching This output is true whenever there is any active non latching shutdown diagnostic that targets the Unit Circuit or any of...

Page 7: ... 71 74 69 66 66 78 Relay Assignments Using Tracer TU Tracer TU Service Tool is used to install the Programmable Relay Option package and assign any of the above lists of events or status to each of the four relays provided with the option See Tracer TU for more information on the Tracer TU service tool The relays to be programmed are referred to by the relay s terminal numbers on the LLID board 1A...

Page 8: ...will run normally when the contact is closed When contact opens the compressor s if operating will go to the RUN UNLOAD operating mode and cycle off Unit operation will be inhibited Closure of the contact will permit the unit to return to normal operation Field supplied contacts for all low voltage connections must be compatible with dry circuit 24 VDC for a 12mA resistive load Refer to the field ...

Page 9: ...be closed when ice making is in progress and open when ice making has been normally terminated either through Ice Termination setpoint being reached or removal of the Ice Making command This relay inform customer equipment with chiller mode changes from ice making to ice complete When contact is provided the chiller will run normally when the contact is open UC800 will accept either an isolated co...

Page 10: ... C DB WB Nominal air flow 2 Conditions Water entering leaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the blower unit Heat exchan...

Page 11: ...A inputs are available as option to set External Current Limit Setpoint The Demand Limit Setting can also be set via the Tracer TD7 or through digital communication with Tracer Comm4 The arbitration of the various sources of demand limit is described in the flow charts at the end of this section The External Current Limit Setpoint may be changed from a remote location by hooking up the analog inpu...

Page 12: ... inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the blower unit Heat exchanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bars Ext...

Page 13: ... Field adjustment of two three and four above is expected to be very infrequent Pre determined factory settings shall be set for all Reset Types Variable definitions CWS Arbitrated chilled water setpoint before any reset has occurred CWS Active chilled water setpoint includes the effect of chilled water reset CWR Amount of chilled water reset also called Degrees of Reset The above quantities are r...

Page 14: ...8 16 8 25 8 25 Unit with electric heater gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 25 1 Conditions Water entering leaving temperature 7 12 C Air inlet temperature 27 19 C DB WB Nominal air flow 2 Conditions Water entering leaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet tem...

Page 15: ... 63 62 56 55 57 67 1 62 58 55 58 51 48 44 61 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 Chilled Water Reset CWR How many Degrees ...

Page 16: ... between the chiller and a Building Automation System BAS An LCI C LLID shall be used to provide gateway functionality between a LonTalk compatible device and the Chiller The inputs outputs include both mandatory and optional network variables as established by the LonMark Functional Chiller Profile 8040 See integration guide for detailed information BACnet Interface BCNT The Building Automation a...

Page 17: ...74 69 66 66 78 Wiring and Port Descriptions for MODBUS BACnet and LonTalk Figure 1 illustrates the UC800 controller ports LEDs rotary switches and wiring terminals The numbered list following Figure 1 Wiring locations and connection ports corresponds to the numbered callouts in the illustration Figure 1 Wiring locations and connection ports of UC800 controller 1 Rotary Switches for setting BACnet ...

Page 18: ...20 3 25 3 25 1 Conditions Water entering leaving temperature 7 12 C Air inlet temperature 27 19 C DB WB Nominal air flow 2 Conditions Water entering leaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is p...

Page 19: ...air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63 62 60 60 53 53 53 64 3 66 65 63 62 56 55 57 67 1 62 58 55 58 51 48 44 61 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 ...

Page 20: ...he availability of each connected sensor relay and actuator Tracer TU is designed to run on a customer s laptop connected to the Tracer control panel with a USB cable Your laptop must meet the following hardware and software requirements 1 GB RAM minimum 1024 x 768 screen resolution CD ROM drive Ethernet 10 100 LAN card An available USB 2 0 port Microsoft Windows 7 Enterprise or Professional opera...

Page 21: ... 39 54 1 56 62 50 48 39 38 36 56 FWD 14 2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 1 57 63 51 49 40 39 37 57 FWD 20 2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 Intake Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63...

Page 22: ... l h mm 24 500 Not available for FWD30 and FWD45 Sound level L M H speed Sound pressure level 5 dB A 36 40 43 38 41 44 46 50 53 47 52 57 47 52 58 Sound power level 5 dB A 46 50 53 48 51 54 56 60 63 57 62 67 57 62 68 Unit dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 644 1133 x 754 1333...

Page 23: ... 39 54 1 56 62 50 48 39 38 36 56 FWD 14 2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 1 57 63 51 49 40 39 37 57 FWD 20 2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 Intake Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63...

Page 24: ...and energy efficient environments Trane offers a broad portfolio of advanced controls and HVAC systems comprehensive building services and parts For more information visit www Trane com 2018 Trane All rights reserved RLC SVU007D GB May 2018 Supersedes RLC SVU007C GB_1017 We are committed to using environmentally conscious print practices that reduce waste ...