Sound power levels

Discharge

Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.

Fan

Power level in dB(A), per Hz frequency band

Overall power

Unit

speed

125

250

500

1000

2000

4000

8000

dB(A)

1

55

50

42

37

37

31

30

46

FWD 08

2

57

54

47

40

30

38

40

50

3

58

57

50

42

32

40

43

53

1

57

51

45

42

34

33

28

48

FWD 10

2

58

54

48

45

38

39

35

51

3

60

58

50

48

40

42

39

54

1

57

51

45

42

34

33

28

48

FWD 12

2

58

54

48

45

38

39

35

51

3

60

58

50

48

40

42

39

54

1

56

62

50

48

39

38

36

56

FWD 14

2

61

66

55

53

47

46

45

60

3

63

69

58

56

50

50

49

63

1

57

63

51

49

40

39

37

57

FWD 20

2

61

66

55

53

47

46

45

60

3

63

69

58

56

50

50

49

63

Intake

Measurement conditions:
Measurements taken at the horizontal air intake.

Fan

Power level in dB(A), per Hz frequency band

Overall power

Unit

speed

125

250

500

1000

2000

4000

8000

dB(A)

1

56

55

55

53

46

45

42

57

FWD 08

2

63

62

60

60

53

53

53

64

3

66

65

63

62

56

55

57

67

1

62

58

55

58

51

48

44

61

FWD 10

2

66

63

60

62

56

55

52

66

3

70

67

63

65

59

59

57

69

1

62

58

55

58

51

48

44

61

FWD 12

2

66

63

60

62

56

55

52

66

3

70

67

63

65

59

59

57

69

1

66

65

65

65

57

50

46

68

FWD 14

2

73

72

69

71

64

59

57

74

3

78

76

73

75

69

64

63

78

1

68

72

64

64

56

52

50

69

FWD 20

2

76

76

68

71

65

61

61

75

3

78

79

71

74

69

66

66

78

Ice Making (Optional)

Evaporator Application defines controls settings: if ICE 
is selected, Ice making is enabled. Specific hardware is 
required for ice making command input and ice making 
status relay output.
UC800 provides auxiliary control thanks to Ice Making 
Status Relay. The normally open contact will be closed 
when ice making is in progress and open when ice 
making has been normally terminated either through 
Ice Termination setpoint being reached or removal of 
the Ice Making command. This relay inform customer 
equipment with chiller mode changes from “ice making” 
to “ice complete”
When contact is provided, the chiller will run normally 
when the contact is open.
UC800 will accept either an isolated contact closure 
(External Ice Making command) or a Remote 
Communicated input (Tracer) to initiate and command 
the Ice Making mode. 
UC800 also provides a “Front Panel Ice Termination 
Setpoint”, settable through Tracer™ TU, and adjustable 
from 20 to 31°F (-6.7 to -0.5°C) in at least 1°F (1°C) 
increments.

Note: 

When the unit runs in Ice Making mode, and the 
evaporator entering water temperature drops below the 
ice termination setpoint, the chiller terminates the Ice 
Making mode and changes to the Ice Making Complete 
Mode.

NOTICE:

Equipment Damage!
Freeze inhibitor must be adequate for leaving water 
temperature unless system components can be 
damaged.
Tracer™ TU must also be used to enable or disable 
Ice Machine Control. This setting does not prevent 
the Tracer from commanding Ice Making mode. Upon 
contact closure, the UC800 will initiate an ice making 
mode, in which the unit runs fully loaded at all times. Ice 
making shall be terminated either by opening the contact 
or based on the entering evaporator water temperature. 
UC800 will not permit the ice making mode to be entered 
again until the unit has been switched out of ice making 
mode.
If, while in ice making mode, the unit gets down to the 
freeze stat setting (water or refrigerant), the unit will 
shut down on a manually resettable diagnostic, just as in 
normal operation.
Connect leads to the proper terminals. Refer to the field 
diagrams which are shipped with the unit. This customer 
supplied contacts must be compatible with 24 VDC, 
12 mA resistive load.

Summary of Contents for Tracer TD7

Page 1: ...RLC SVU007D GB Tracer TD7 with UC 800 User Guide Original instructions ...

Page 2: ... 754 1333 x 864 1333 x 1008 1333 1133 Height mm 260 310 360 460 660 Weight kg 32 46 61 76 118 Colour galvanised steel Recommended fuse size Unit alone aM gI A 8 16 8 16 8 16 8 25 8 25 Unit with electric heater gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 25 1 Conditions Water entering leaving temperature 7 12 C Air inlet temperature 27 19 C DB WB Nominal air flow 2 Conditions Water entering le...

Page 3: ... storing component provided by Trane or others refer to the appropriate manufacturer s literature for allowable waiting periods for discharge of capacitors Verify with an appropriate voltmeter that all capacitors have discharged DC bus capacitors retain hazardous voltages after input power has been disconnected Follow proper lockout tagout procedures to ensure the power cannot be inadvertently ene...

Page 4: ...r temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bars Installer Supplied Components InterconnectingWiring Installer Supplied Components Customer wiring interface connections are shown in the electrical schematics and connection diagrams that are shipped with the unit The installer must provide the following components if not ordered with the unit Power supply wiring in co...

Page 5: ... 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 Installer Supplied Components InterconnectingWiring If water flow is not established in 20 minutes for normal transition the UC800 de energizes ...

Page 6: ... The relay will be energized when the event state occurs Table 3 Chiller event status descriptions Alarm Latching This output is true whenever there is any active latching shutdown diagnostic that targets the Unit Circuit or any of the Compressors on a circuit Alarm NonLatching This output is true whenever there is any active non latching shutdown diagnostic that targets the Unit Circuit or any of...

Page 7: ... 71 74 69 66 66 78 Relay Assignments Using Tracer TU Tracer TU Service Tool is used to install the Programmable Relay Option package and assign any of the above lists of events or status to each of the four relays provided with the option See Tracer TU for more information on the Tracer TU service tool The relays to be programmed are referred to by the relay s terminal numbers on the LLID board 1A...

Page 8: ...will run normally when the contact is closed When contact opens the compressor s if operating will go to the RUN UNLOAD operating mode and cycle off Unit operation will be inhibited Closure of the contact will permit the unit to return to normal operation Field supplied contacts for all low voltage connections must be compatible with dry circuit 24 VDC for a 12mA resistive load Refer to the field ...

Page 9: ...be closed when ice making is in progress and open when ice making has been normally terminated either through Ice Termination setpoint being reached or removal of the Ice Making command This relay inform customer equipment with chiller mode changes from ice making to ice complete When contact is provided the chiller will run normally when the contact is open UC800 will accept either an isolated co...

Page 10: ... C DB WB Nominal air flow 2 Conditions Water entering leaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the blower unit Heat exchan...

Page 11: ...A inputs are available as option to set External Current Limit Setpoint The Demand Limit Setting can also be set via the Tracer TD7 or through digital communication with Tracer Comm4 The arbitration of the various sources of demand limit is described in the flow charts at the end of this section The External Current Limit Setpoint may be changed from a remote location by hooking up the analog inpu...

Page 12: ... inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the blower unit Heat exchanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bars Ext...

Page 13: ... Field adjustment of two three and four above is expected to be very infrequent Pre determined factory settings shall be set for all Reset Types Variable definitions CWS Arbitrated chilled water setpoint before any reset has occurred CWS Active chilled water setpoint includes the effect of chilled water reset CWR Amount of chilled water reset also called Degrees of Reset The above quantities are r...

Page 14: ...8 16 8 25 8 25 Unit with electric heater gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 25 1 Conditions Water entering leaving temperature 7 12 C Air inlet temperature 27 19 C DB WB Nominal air flow 2 Conditions Water entering leaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet tem...

Page 15: ... 63 62 56 55 57 67 1 62 58 55 58 51 48 44 61 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 Chilled Water Reset CWR How many Degrees ...

Page 16: ... between the chiller and a Building Automation System BAS An LCI C LLID shall be used to provide gateway functionality between a LonTalk compatible device and the Chiller The inputs outputs include both mandatory and optional network variables as established by the LonMark Functional Chiller Profile 8040 See integration guide for detailed information BACnet Interface BCNT The Building Automation a...

Page 17: ...74 69 66 66 78 Wiring and Port Descriptions for MODBUS BACnet and LonTalk Figure 1 illustrates the UC800 controller ports LEDs rotary switches and wiring terminals The numbered list following Figure 1 Wiring locations and connection ports corresponds to the numbered callouts in the illustration Figure 1 Wiring locations and connection ports of UC800 controller 1 Rotary Switches for setting BACnet ...

Page 18: ...20 3 25 3 25 1 Conditions Water entering leaving temperature 7 12 C Air inlet temperature 27 19 C DB WB Nominal air flow 2 Conditions Water entering leaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is p...

Page 19: ...air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63 62 60 60 53 53 53 64 3 66 65 63 62 56 55 57 67 1 62 58 55 58 51 48 44 61 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 ...

Page 20: ...he availability of each connected sensor relay and actuator Tracer TU is designed to run on a customer s laptop connected to the Tracer control panel with a USB cable Your laptop must meet the following hardware and software requirements 1 GB RAM minimum 1024 x 768 screen resolution CD ROM drive Ethernet 10 100 LAN card An available USB 2 0 port Microsoft Windows 7 Enterprise or Professional opera...

Page 21: ... 39 54 1 56 62 50 48 39 38 36 56 FWD 14 2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 1 57 63 51 49 40 39 37 57 FWD 20 2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 Intake Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63...

Page 22: ... l h mm 24 500 Not available for FWD30 and FWD45 Sound level L M H speed Sound pressure level 5 dB A 36 40 43 38 41 44 46 50 53 47 52 57 47 52 58 Sound power level 5 dB A 46 50 53 48 51 54 56 60 63 57 62 67 57 62 68 Unit dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 644 1133 x 754 1333...

Page 23: ... 39 54 1 56 62 50 48 39 38 36 56 FWD 14 2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 1 57 63 51 49 40 39 37 57 FWD 20 2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 Intake Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63...

Page 24: ...and energy efficient environments Trane offers a broad portfolio of advanced controls and HVAC systems comprehensive building services and parts For more information visit www Trane com 2018 Trane All rights reserved RLC SVU007D GB May 2018 Supersedes RLC SVU007C GB_1017 We are committed to using environmentally conscious print practices that reduce waste ...

Reviews: