Figure 250:
HSR ring
18.4
Merging unit
18.4.1
Introduction
GUID-E630C16F-EDB8-40AE-A8A2-94189982D15F v1
The IEC/UCA 61850-9-2LE process bus communication protocol enables an IED to
communicate with devices providing measured values in digital format, commonly
known as Merging Units (MU). The rear access points are used for the communication.
The merging units (MU) are called so because they can gather analog values from one
or more measuring transformers, sample the data and send the data over process bus to
other clients (or subscribers) in the system. Some merging units are able to get data
from classical measuring transformers, others from non-conventional measuring
transducers and yet others can pick up data from both types.
Section 18
1MRK 511 408-UUS A
Ethernet
616
Phasor measurement unit RES670 2.2 ANSI
Technical manual