visible and possible to make only if Easy GOOSE engineering is
enabled. For instructions on how to enable Easy GOOSE engineering in
PCM600, refer to the
Engineering Manual
.
PID-6829-INPUTSIGNALS v3
Table 482:
GOOSEINTRCV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
SRCINTOUT
INTEGER
0
Source to integer output
PID-6829-OUTPUTSIGNALS v3
Table 483:
GOOSEINTRCV Output signals
Name
Type
Description
INTOUT
INTEGER
Integer output
DATAVALID
BOOLEAN
Data valid for integer output
COMMVALID
BOOLEAN
Communication valid for integer output
TEST
BOOLEAN
Test output
19.4.8.5
Settings
PID-6829-SETTINGS v3
Table 484:
GOOSEINTRCV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
19.4.8.6
Operation principle
GUID-5BBDF772-3B3E-4F7C-ABE9-18CE3C1A2E2D v4
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
Data Value
Data Valid
Comm Valid
Test
Incoming data with q=Normal
Updated
1
1
0
Incoming data with q=oldData
Freeze
0
1
0
Incoming data with q=Invalid
Freeze
0
1
0
Incoming data with q=test
Freeze
0
1
1
Table continues on next page
1MRK 511 408-UUS A
Section 19
Station communication
Phasor measurement unit RES670 2.2 ANSI
637
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...