INPUT14
BOOLEAN
0
Binary input 14
INPUT15
BOOLEAN
0
Binary input 15
INPUT16
BOOLEAN
0
Binary input 16
PID-4127-OUTPUTSIGNALS v3
Table 247:
WRNCALH Output signals
Name
Type
Description
WARNING
BOOLEAN
OR function betweeen inputs 1 to 16
15.5.5
Settings
PID-4127-SETTINGS v3
Table 248:
WRNCALH Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
15.5.6
Operation principle
GUID-71C65C20-7B6C-499F-BFCD-E418AA55F7EC v2
The logic for group warning WRNCALH block is provided with 16 input signals and 1
WARNING output signal. The function block incorporates internal logic OR gate in
order to provide grouping of connected input signals to the output WARNING signal
from the function block.
When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the
WARNING output signal will get logical value 1.
The function has a drop-off delay of 200 ms when all inputs are reset to provide a
steady signal.
WARNING
1
ANSI13000192-1-en.vsd
INPUT1
INPUT16
200 ms
0
ANSI13000192 V1 EN-US
1MRK 511 408-UUS A
Section 15
Logic
Phasor measurement unit RES670 2.2 ANSI
427
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...