9.2.8
Technical data
IP13013-1 v1
M13304-1 v14
Table 161:
OV2PTOV (59) technical data
Function
Range or value
Accuracy
Trip voltage, step 1 and 2
(1.0-200.0)% of
VBase
±0.5% of V
n
at V ≤ V
n
±0.5% of V at V > V
n
Absolute hysteresis
(0.0–50.0)% of
VBase
±0.5% of V
n
at V ≤ V
n
±0.5% of V at V > V
n
Inverse time characteristics for steps 1
and 2, see table
-
See table
Definite time delay, low step (step 1) at 0
to 1.2 x V
set
(0.00 - 6000.00) s
±0.2% or ±45 ms
whichever is greater
Definite time delay, high step (step 2) at 0
to 1.2 x V
set
(0.000-60.000) s
±0.2% or ±45 ms
whichever is greater
Minimum trip time, Inverse characteristics
(0.000-60.000) s
±0.2% or ±45 ms
whichever is greater
Trip time, pickup at 0 to 2 x V
set
Min. = 15 ms
Max. = 30 ms
-
Reset time, pickup at 2 x V
set
to 0
Min. = 15 ms
Max. = 30 ms
-
Trip time, pickup at 0 to 1.2 x V
set
Min. = 20 ms
Max. = 35 ms
-
Reset time, , pickup at 1.2 x V
set
to 0
Min. = 5 ms
Max. = 25 ms
-
Critical impulse time
10 ms typically at 0 to 2 x V
set
-
Impulse margin time
15 ms typically
-
1MRK 511 408-UUS A
Section 9
Voltage protection
Phasor measurement unit RES670 2.2 ANSI
299
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...