Each of the functions includes the blocking from the TESTMODE function block.
The functions can also be blocked from sending events over IEC 61850 station bus to
prevent filling station and SCADA databases with test events, for example during a
commissioning or maintenance test.
22.4
IED identifiers TERMINALID
IP15060-1 v2
22.4.1
Functionality
M15324-3 v6
IED identifiers (TERMINALID) function allows the user to identify the individual IED
in the system, not only in the substation, but in a whole region or a country.
Use only characters A-Z, a-z and 0-9 in station, object and unit names.
22.4.2
Settings
GUID-3C49A222-FFE4-492B-A96C-9E9965FA2CB4 v2
PID-6801-SETTINGS v1
Table 603:
TERMINALID Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
StationName
0 - 18
-
1
Station name
Station name
StationNumber
0 - 99999
-
1
0
Station number
ObjectName
0 - 18
-
1
Object name
Object name
ObjectNumber
0 - 99999
-
1
0
Object number
UnitName
0 - 18
-
1
Unit name
Unit name
UnitNumber
0 - 99999
-
1
0
Unit number
IEDMainFunType
0 - 255
-
1
0
IED main function type for IEC60870-5-103
TechnicalKey
0 - 16
-
1
AA0B0Q0A0
Technical key (part 1)
0 - 16
-
1
Technical key (part 2)
0 - 16
-
1
Technical key (part 3)
0 - 16
-
1
Technical key (part 4)
1MRK 511 408-UUS A
Section 22
Basic IED functions
Phasor measurement unit RES670 2.2 ANSI
779
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...