19.4.10
GOOSE function block to receive a single point value
GOOSESPRCV
19.4.10.1
Identification
GUID-F2B30A70-842E-435E-8FAB-B1E58B9C0164 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE function block to receive a
single point value
GOOSESPRCV
-
-
19.4.10.2
Functionality
GUID-0C99A106-C131-45D3-9B81-6B188E35EB34 v3
GOOSESPRCV is used to receive a single point value using IEC 61850 protocol via
GOOSE.
19.4.10.3
Function block
GUID-A414F31A-323F-4684-BADA-46F9C5E2B0E8 v1
IEC10000248-2-en.vsd
GOOSESPRCV
BLOCK
^SRCSPOUT
^SPOUT
DATAVALID
COMMVALID
TEST
IEC10000248 V2 EN-US
Figure 259:
GOOSESPRCV function block
19.4.10.4
Signals
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1
Except for the BLOCK input, the rest of the inputs of this GOOSE
function block are used for GOOSE connections. These connections are
visible and possible to make only if Easy GOOSE engineering is
enabled. For instructions on how to enable Easy GOOSE engineering in
PCM600, refer to the
Engineering Manual
.
PID-6832-INPUTSIGNALS v3
Table 488:
GOOSESPRCV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
SRCSPOUT
BOOLEAN
0
Source to single point output
1MRK 511 408-UUS A
Section 19
Station communication
Phasor measurement unit RES670 2.2 ANSI
641
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...