![ABB Relion RES670 Technical Manual Download Page 508](http://html.mh-extra.com/html/abb/relion-res670/relion-res670_technical-manual_4485508.webp)
Name
Values (Range)
Unit
Step
Default
Description
VABAngDbRepInt
1 - 100000
s
1
10
Cyclic report interval (s)
VBC_DbRepInt
1 - 100000
Type
1
10
Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
VBC_ZeroDb
0 - 100000
m%
500
1000
Magnitude zero point clamping in 0,001% of
range
VBC_Min
0.0 - 200.0
%VB
0.1
50.0
Minimum value in % of VBase
VBC_Max
0.0 - 200.0
%VB
0.1
200.0
Maximum value in % of VBase
VBC_RepTyp
Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
-
-
Cyclic
Reporting type
VBCAngDbRepInt
1 - 100000
s
1
10
Cyclic report interval (s)
VCA_DbRepInt
1 - 100000
Type
1
10
Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
VCA_ZeroDb
0 - 100000
m%
500
1000
Magnitude zero point clamping in 0,001% of
range
VCA_Min
0.0 - 200.0
%VB
0.1
50.0
Minimum value in % of VBase
VCA_Max
0.0 - 200.0
%VB
0.1
200.0
Maximum value in % of VBase
VCA_RepTyp
Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
-
-
Cyclic
Reporting type
VCAAngDbRepInt
1 - 100000
s
1
10
Cyclic report interval (s)
Table 380:
VMMXU Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
VAB_HiHiLim
0.0 - 200.0
%VB
0.1
150.0
High High limit in % of UBase
VAB_HiLim
0.0 - 200.0
%VB
0.1
120.0
High limit in % of VBase
VAB_LowLim
0.0 - 200.0
%VB
0.1
80.0
Low limit in % of VBase
VAB_LowLowLim
0.0 - 200.0
%VB
0.1
60.0
Low Low limit in % of VBase
VMagComp100
-10.000 - 10.000
%
0.001
0.000
Magnitude factor to calibrate voltage at 100%
of Vn
VAB_LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range, common for
all limits
VBC_HiHiLim
0.0 - 200.0
%VB
0.1
150.0
High High limit in % of UBase
VBC_HiLim
0.0 - 200.0
%VB
0.1
120.0
High limit in % of VBase
VBC_LowLim
0.0 - 200.0
%VB
0.1
80.0
Low limit in % of VBase
VBC_LowLowLim
0.0 - 200.0
%VB
0.1
60.0
Low Low limit in % of VBase
Table continues on next page
Section 16
1MRK 511 408-UUS A
Monitoring
502
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...