Name
Values (Range)
Unit
Step
Default
Description
TimeChar
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
-
-
IEC Norm. inv.
Operation curve selection for IDMT operation
t_MinTripDelay
0.000 - 60.000
s
0.001
0.040
Minimum operate time for IEC IDMT curves,
in sec
TDIN
0.05 - 2.00
-
0.01
1.00
IDMT time mult for non-dir res over current
protection
OpVN
Disabled
Enabled
-
-
Disabled
Operation of non-directional residual
overvoltage protection
VN_PU
1.00 - 200.00
%VB
0.01
20.00
Set level for non-directional residual over
voltage in % of VBase
tVN
0.000 - 60.000
s
0.001
0.100
Time delay for non-directional residual over
voltage, in sec
INRelPU
0.25 - 200.00
%IB
0.01
1.00
Residual release current for all directional
modes in % of IBase
VNRelPU
1.00 - 300.00
%VB
0.01
3.00
Residual release voltage for all direction
modes in % of VBase
Table 116:
SDEPSDE (67N) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
tReset
0.000 - 60.000
s
0.001
0.040
Time delay used for reset of definite timers, in
sec
tPCrv
0.005 - 3.000
-
0.001
1.000
Setting P for customer programmable curve
tACrv
0.005 - 200.000
-
0.001
13.500
Setting A for customer programmable curve
tBCrv
0.00 - 20.00
-
0.01
0.00
Setting B for customer programmable curve
tCCrv
0.1 - 10.0
-
0.1
1.0
Setting C for customer programmable curve
ResetTypeCrv
Immediate
IEC Reset
ANSI reset
-
-
IEC Reset
Reset mode when current drops off.
tPRCrv
0.005 - 3.000
-
0.001
0.500
Setting PR for customer programmable curve
tTRCrv
0.005 - 100.000
-
0.001
13.500
Setting TR for customer programmable curve
tCRCrv
0.1 - 10.0
-
0.1
1.0
Setting CR for customer programmable curve
1MRK 511 408-UUS A
Section 8
Current protection
Phasor measurement unit RES670 2.2 ANSI
233
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...