![ABB Relion RES670 Technical Manual Download Page 667](http://html.mh-extra.com/html/abb/relion-res670/relion-res670_technical-manual_4485667.webp)
•
Ok[0]
indicates that the merging unit samples are received from the merging
unit and are accepted.
•
ERROR[1]
indicates that the merging unit samples are generated by internal
substitution.
•
SYNCH:
•
OK[0]
indicates
•
when
SyncLostMode = Block
, and the time quality of the hardware is
within the set value [
SyncAccLevel=1us, 4us
or
Unspecified
]
•
when
SyncLostMode = BlockOnLostUTC
, the time quality of the
hardware is within the set value [
SyncAccLevel=1us
,
4us
or
Unspecified
]
[AND]
IED receives global common time[UTC] from
any of the
FineSyncSource
like IRIG-B, PTP or GPS.
•
when
SyncLostMode = NoBlock
•
ERROR[1] indicates
•
when
SyncLostMode = Block
, and the time quality of the hardware is
not within the set value [
SyncAccLevel=1us
,
4us
or
Unspecified
]
•
when
SyncLostMode = BlockonLostUTC
, the time quality of the
hardware is not within the set value [
SyncAccLevel=1us
,
4us
or
Unspecified
]
[OR]
IED doesn't receive global common time[UTC]
from any of the
FineSyncSource
like IRIG-B, PTP or GPS.
•
SMPLLOST:
•
NO[0]
indicates that the merging unit samples are received from the merging
unit and are accepted
•
YES[1]
indicates
•
when merging unit data are generated by internal substitution
•
when one/more channel's Quality is not good
•
when merging unit is in Testmode/detailed
quality=Test
, IED is not in
test mode
•
MUSYNCH:
•
OK[0]
indicates
•
when
SyncLostMode = Block/BlockOnLostUTC
, the time quality of
the hardware is within the set value [
SyncAccLevel=1us
,
4us
or
Unspecified
]
[AND]
merging unit is time synchronized [
smpSynch
flag in datastream is not equal to 0]
•
when
SyncLostMode = NoBlock
, the merging unit samples are
received
•
ERROR[1]
indicates
•
when
SyncLostMode = Block/BlockOnLostUTC
, the time quality of
the hardware is not within the set value [
SyncAccLevel=1us
,
4us
or
1MRK 511 408-UUS A
Section 19
Station communication
Phasor measurement unit RES670 2.2 ANSI
661
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...