Autorecloser ON/OFF
•
Teleprotection ON/OFF
•
Protection ON/OFF
•
LED reset
•
Characteristics 1 - 4 (Setting groups)
•
File transfer (disturbance files)
•
Time synchronization
For detailed information about IEC 60870-5-103, refer to the IEC 60870 standard part
5: Transmission protocols, and to the section 103: Companion standard for the
informative interface of protection equipment.
IEC 60870-5-103 vendor specific implementation
M11874-23 v4
The signal and setting tables specify the information types supported by the IEDs with
the communication protocol IEC 60870-5-103 implemented.
The information types are supported when corresponding functions are included in the
protection and control IED.
Be aware of that different cycle times for function blocks must be
considered to ensure correct time stamping.
Commands in control direction
M11874-27 v1
Commands in control direction, I103IEDCMD
M11874-29 v6
Command block in control direction with defined output signals.
Number of instances: 1
Function type is selected with parameter
FunctionType
.
Information number is defined for each output signals.
Table 537:
I103IEDCMD supported indications
INF
Description
19
LED Reset
23
Activate setting group 1
24
Activate setting group 2
25
Activate setting group 3
26
Activate setting group 4
Function commands in control direction, pre-defined I103CMD
M11874-53 v6
1MRK 511 408-UUS A
Section 19
Station communication
Phasor measurement unit RES670 2.2 ANSI
709
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...