Events are produced according to set event masks. The event masks are treated
commonly for both the LON and SPA communication. An
EventMask
can be set
individually for each input channel. These settings are available:
•
NoEvents
•
OnSet
•
OnReset
•
OnChange
•
AutoDetect
It is possible to define which part of the EVENT function generates the events. This
can be performed individually for communication types
SPAChannelMask
and
LONChannelMask
. For each communication type these settings are available:
•
Disabled
•
Channel 1-8
•
Channel 9-16
•
Channel 1-16
For LON communication, events are normally sent to station level at change. It is also
possible to set a time for cyclic sending of the events individually for each input
channel.
To protect the SA system from signals with a high change rate that can easily saturate
the EVENT function or the communication subsystems behind it, a quota limiter is
implemented. If an input creates events at a rate that completely consume the granted
quota then further events from the channel will be blocked. This block will be removed
when the input calms down and the accumulated quota reach 66% of the maximum
burst quota. The maximum burst quota per input channel is 45 events per second.
16.6
Disturbance report DRPRDRE
IP14584-1 v2
16.6.1
Identification
M16055-1 v8
Function description
IEC 61850 identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Disturbance report
DRPRDRE
-
-
Disturbance report
A1RADR - A4RADR
-
-
Disturbance report
B1RBDR - B22RBDR
-
-
Section 16
1MRK 511 408-UUS A
Monitoring
552
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...