Set value for the
parameter
CurrentInput
Comment
11
PhaseB-PhaseC
CVGAPC function will measure the current phasor internally calculated as
the vector difference between the phase B current phasor and phase C
current phasor (I
B
-I
C
)
12
PhaseC-PhaseA
CVGAPC function will measure the current phasor internally calculated as
the vector difference between the phase C current phasor and phase A
current phasor ( I
C
-I
A
)
13
MaxPh-Ph
CVGAPC function will measure ph-ph current phasor with the maximum
magnitude
14
MinPh-Ph
CVGAPC function will measure ph-ph current phasor with the minimum
magnitude
15
UnbalancePh-Ph
CVGAPC function will measure magnitude of unbalance current, which is
internally calculated as the algebraic magnitude difference between the ph-
ph current phasor with maximum magnitude and ph-ph current phasor with
minimum magnitude. Phase angle will be set to 0° all the time
The user can select to measure one of the voltage quantities shown in table
Table 190:
Voltage selection for CVGAPC function
Set value for the
parameter
VoltageInput
Comment
1
PhaseA
CVGAPC function will measure the phase A voltage phasor
2
PhaseB
CVGAPC function will measure the phase B voltage phasor
3
PhaseC
CVGAPC function will measure the phase C voltage phasor
4
PosSeq
CVGAPC function will measure internally calculated positive sequence
voltage phasor
5
-NegSeq
CVGAPC function will measure internally calculated negative sequence
voltage phasor. This voltage phasor will be intentionally rotated for 180° in
order to enable easier settings for the directional feature when used.
6
-3ZeroSeq
CVGAPC function will measure internally calculated zero sequence voltage
phasor multiplied by factor 3. This voltage phasor will be intentionally
rotated for 180° in order to enable easier settings for the directional feature
when used.
7
MaxPh
CVGAPC function will measure voltage phasor of the phase with maximum
magnitude
8
MinPh
CVGAPC function will measure voltage phasor of the phase with minimum
magnitude
9
UnbalancePh
CVGAPC function will measure magnitude of unbalance voltage, which is
internally calculated as the algebraic magnitude difference between the
voltage phasor of the phase with maximum magnitude and voltage phasor
of the phase with minimum magnitude. Phase angle will be set to 0° all the
time
Table continues on next page
1MRK 511 408-UUS A
Section 11
Multipurpose protection
Phasor measurement unit RES670 2.2 ANSI
337
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...