![ABB Relion RES670 Technical Manual Download Page 584](http://html.mh-extra.com/html/abb/relion-res670/relion-res670_technical-manual_4485584.webp)
For each of the analog signals,
Operation
=
Enabled
means that it is recorded by the
disturbance recorder. The trigger is independent of the setting of
Operation
, and
triggers even if operation is set to
Disabled
. Both undervoltage and overvoltage can be
used as trigger conditions. The same applies for the current signals.
If
Operation
=
Disabled
, no waveform (samples) will be recorded and reported in
graph. However, Trip value, pre-fault and fault value will be recorded and reported.
The input channel can still be used to trig the disturbance recorder.
If
Operation
=
Enabled
, waveform (samples) will also be recorded and reported in
graph.
The analog signals are presented only in the disturbance recording, but they affect the
entire disturbance report when being used as triggers.
Binary signals
M12155-162 v9
Up to 352 binary signals can be selected to be handled by disturbance report. The
signals can be selected from internal logical and binary input signals. A binary signal is
selected to be recorded when:
•
the corresponding function block is included in the configuration
•
the signal is connected to the input of the function block
Each of the 352 signals can be selected as a trigger of the disturbance report
(
Operation
=
Operation—>TrigDR =Enabled
). A binary signal can be selected to
activate the red LED on the local HMI (
SetLED
=
Enabled
).
The selected signals are presented in the event recorder, sequential of events and the
disturbance recording. But they affect the whole disturbance report when they are used
as triggers. The indications are also selected from these 352 signals with local HMI
IndicationMask = Show/Hide
.
Trigger signals
M12155-164 v2
The trigger conditions affect the entire disturbance report, except the sequential of
events, which runs continuously. As soon as at least one trigger condition is fulfilled, a
complete disturbance report is recorded. On the other hand, if no trigger condition is
fulfilled, there is no disturbance report, no indications, and so on. This implies the
importance of choosing the right signals as trigger conditions.
A trigger can be of type:
•
Manual trigger
•
Binary-signal trigger
•
Analog-signal trigger (over/under function)
Section 16
1MRK 511 408-UUS A
Monitoring
578
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...