15.2
General start matrix block SMAGAPC
15.2.1
Identification
GUID-C6D3DE50-03D2-4F27-82FF-623E81D019F4 v1
Function Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Generat start matrix block
SMAGAPC
-
-
15.2.2
Functionality
GUID-BA516165-96DE-4CD9-979B-29457C7653C0 v3
The Start Matrix (SMAGAPC) merges start and directional output signals from
different application functions and creates a common start and directional output signal
(
STDIR
) to be connected to the Trip function, see Figure
The purpose of this functionality is to provide general start and directional information
for the IEC 61850 trip logic data model SMPPTRC.
15.2.3
Function block
GUID-99B1DF71-F7C4-4954-8688-BC709C3C2A16 v1
ANSI16000165=1=en=Original.vsdx
SMAGAPC
BLOCK
PU_DIR1
PU_DIR2
PU_DIR3
PU_DIR4
PU_DIR5
PU_DIR6
PU_DIR7
PU_DIR8
PU_DIR9
PU_DIR10
PU_DIR11
PU_DIR12
PU_DIR13
PU_DIR14
PU_DIR15
PU_DIR16
CND
ANSI16000165 V1 EN-US
Figure 149:
SMAGAPC function block
1MRK 511 408-UUS A
Section 15
Logic
Phasor measurement unit RES670 2.2 ANSI
411
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...