Data Value
Data Valid
Comm Valid
Test
Incoming data with q=test+oldData
Freeze
0
1
1
Receiver in block
Freeze
0
1
0
Receiver in block and communication
error
Freeze
0
0
0
Receiver in test mode and incoming data
with q= Normal
Updated
1
1
0
Receiver in test mode and incoming data
with q= Test
Updated
1
1
1
Communication Error
Freeze
0
0
0
The input of this GOOSE block must be linked either in SMT by means
of a cross or in ACT by means of a GOOSE connection (if easy
GOOSE engineering is enabled) to receive the integer values.
The implementation for IEC 61850 quality data handling is restricted to
a simple level. If quality data validity is GOOD then the DATAVALID
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.
19.4.9
GOOSE function block to receive a measurand value
GOOSEMVRCV
19.4.9.1
Identification
GUID-B1FFBE08-C823-4A58-9FE0-A9A20DA6BB44 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE function block to receive a
measurand value
GOOSEMVRCV
-
-
19.4.9.2
Functionality
GUID-759CB016-2B4D-4D98-82E1-592044983D53 v3
GOOSEMVRCV is used to receive measured value using IEC 61850 protocol via
GOOSE.
Section 19
1MRK 511 408-UUS A
Station communication
638
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...