16.2.2
Functionality
GUID-0692CD0D-F33E-4370-AC91-B216CAAAFC28 v6
Insulation supervision for gas medium (SSIMG (63)) is used for monitoring the circuit
breaker condition. Binary information based on the gas pressure in the circuit breaker
is used as input signals to the function. In addition, the function generates alarms based
on received information.
16.2.3
Function block
GUID-94B75A6D-973D-4F1F-8643-F2128AD31CC4 v3
SSIMG (63)
BLOCK
BLKALM
SENPRES
SENTEMP
SENPRESALM
SENPRESLO
SETP LO
SETTLO
RESETLO
LOCKOU T
PRESLO
TEMPLO
ALARM
PRESALM
TEMPALM
PRESSURE
TEMP
ANSI09000129-2-en.vsdx
ANSI09000129 V2 EN-US
Figure 204:
SSIMG (63) function block
16.2.4
Signals
GUID-89749F71-CAEB-4A57-A1F0-148CCF68E97E v2
PID-6950-INPUTSIGNALS v6
Table 399:
SSIMG Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
BLKALM
BOOLEAN
0
Block all the alarms
SENPRES
REAL
0.0
Pressure input from CB
SENTEMP
REAL
0.0
Temperature of the insulation medium from CB
SENPRESALM
BOOLEAN
0
Pressure alarm signal
SENPRESLO
BOOLEAN
0
Pressure lockout signal
SETPLO
BOOLEAN
0
Set pressure lockout
SETTLO
BOOLEAN
0
Set temperature lockout
RESETLO
BOOLEAN
0
Reset pressure and temperature lockout
1MRK 511 408-UUS A
Section 16
Monitoring
Phasor measurement unit RES670 2.2 ANSI
525
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...