The input of this GOOSE block must be linked either in SMT by means
of a cross or in ACT by means of a GOOSE connection (if easy
GOOSE engineering is enabled) to receive the double point values.
The implementation for IEC 61850 quality data handling is restricted to
a simple level. If quality data validity is GOOD then the DATAVALID
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.
19.4.8
GOOSE function block to receive an integer value
GOOSEINTRCV
19.4.8.1
Identification
GUID-93A1E81B-1DE8-483A-BB3B-DB771EE66DC1 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE function block to receive an
integer value
GOOSEINTRCV
-
-
19.4.8.2
Functionality
GUID-27B1ED7A-C8E8-499E-89C1-C656FB0337F8 v3
GOOSEINTRCV is used to receive an integer value using IEC 61850 protocol via
GOOSE.
19.4.8.3
Function block
GUID-56F0C9F7-98F3-4091-B071-53CA5074DC8F v1
IEC10000250-2-en.vsd
GOOSEINTRCV
BLOCK
^SRCINTOUT
^INTOUT
DATAVALID
COMMVALID
TEST
IEC10000250 V2 EN-US
Figure 257:
GOOSEINTRCV function block
19.4.8.4
Signals
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1
Except for the BLOCK input, the rest of the inputs of this GOOSE
function block are used for GOOSE connections. These connections are
Section 19
1MRK 511 408-UUS A
Station communication
636
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...