19.7.11
IED commands for IEC 60870-5-103 I103IEDCMD
19.7.11.1
Functionality
GUID-19AD44B2-21D6-4DB0-AD74-1578DA30C100 v5
I103IEDCMD is a command block in control direction with defined IED functions. All
outputs are pulsed and they are NOT stored. Pulse length is fixed to 400ms.
19.7.11.2
Identification
GUID-0D0B2477-1B0C-48F3-B047-CCF9C7A71856 v1
Function description
Function block
name
IEC 60617
identification
ANSI/IEEE C37.2
device number
IED commands for IEC 60870-5-103
I103IEDCMD
-
-
19.7.11.3
Function block
GUID-52D27CDA-8805-48FA-99BE-2E05A438B0C7 v1
IEC10000283-1-en.vsd
I103IEDCMD
BLOCK
19-LEDRS
23-GRP1
24-GRP2
25-GRP3
26-GRP4
IEC10000283 V1 EN-US
Figure 277:
I103IEDCMD function block
19.7.11.4
Signals
PID-3788-INPUTSIGNALS v5
Table 524:
I103IEDCMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of commands
PID-3788-OUTPUTSIGNALS v5
Table 525:
I103IEDCMD Output signals
Name
Type
Description
19-LEDRS
BOOLEAN
Information number 19, reset LEDs
23-GRP1
BOOLEAN
Information number 23, activate setting group 1
24-GRP2
BOOLEAN
Information number 24, activate setting group 2
25-GRP3
BOOLEAN
Information number 25, activate setting group 3
26-GRP4
BOOLEAN
Information number 26, activate setting group 4
1MRK 511 408-UUS A
Section 19
Station communication
Phasor measurement unit RES670 2.2 ANSI
701
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...