23.2.11
mA input module (MIM)
IP14537-1 v1
23.2.11.1
Introduction
M15020-3 v4
The milli-ampere input module is used to interface transducer signals in the –20 to +20
mA range from for example OLTC position, temperature or pressure transducers. The
module has six independent, galvanically separated channels.
23.2.11.2
Design
SEMOD55434-1 v1
M6380-3 v5
The Milliampere Input Module has six independent analog channels with separated
protection, filtering, reference, A/D-conversion and optical isolation for each input
making them galvanically isolated from each other and from the rest of the module.
For configuration of the input signals, refer to section
The analog inputs measure DC current in the range of +/- 20 mA. The A/D converter
has a digital filter with selectable filter frequency. All inputs are calibrated separately
The filter parameters and the calibration factors are stored in a non-volatile memory on
the module.
If mA inputs should report measurements, dead band
MaxReportT
should be set to 0 s.
If
MaxReportT
is set to any value higher than 0 s, all the inputs will have cyclic
reporting completely disregarding the settings
EnDeadBandChx
and
DeadBandChx
.
That is, if
MaxReportT
is set to 1 s, and wants certain channel to report values as dead
band by setting the parameter
EnDeadBandChx
to ON, that channel will still report
values as cyclic, completely ignoring the
EnDeadBandChx
parameter.
The calibration circuitry monitors the module temperature and starts an automatical
calibration procedure if the temperature drift is outside the allowed range.
Section 23
1MRK 511 408-UUS A
IED hardware
840
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...