![ABB Relion RES670 Technical Manual Download Page 849](http://html.mh-extra.com/html/abb/relion-res670/relion-res670_technical-manual_4485849.webp)
Name
Values (Range)
Unit
Step
Default
Description
ValueMaxCh2
-10000000000.000
-
10000000000.000
-
0.001
20.000
Max primary value corr. to IMaxCh2
EnDeadBandCh3
Disabled
Enabled
-
-
Disabled
Enable amplitude deadband reporting for
channel 3
DeadBandCh3
0.00 - 20.00
mA
0.01
1.00
Deadband amplitude for channel 3
IMinCh3
-25.00 - 25.00
mA
0.01
4.00
Min current of transducer for Channel 3
IMaxCh3
-25.00 - 25.00
mA
0.01
20.00
Max current of transducer for Channel 3
ValueMinCh3
-10000000000.000
-
10000000000.000
-
0.001
4.000
Min primary value corr. to IMinCh3
ValueMaxCh3
-10000000000.000
-
10000000000.000
-
0.001
20.000
Max primary value corr. to IMaxCh3
EnDeadBandCh4
Disabled
Enabled
-
-
Disabled
Enable amplitude deadband reporting for
channel 4
DeadBandCh4
0.00 - 20.00
mA
0.01
1.00
Deadband amplitude for channel 4
IMinCh4
-25.00 - 25.00
mA
0.01
4.00
Min current of transducer for Channel 4
IMaxCh4
-25.00 - 25.00
mA
0.01
20.00
Max current of transducer for Channel 4
ValueMinCh4
-10000000000.000
-
10000000000.000
-
0.001
4.000
Min primary value corr. to IMinCh4
ValueMaxCh4
-10000000000.000
-
10000000000.000
-
0.001
20.000
Max primary value corr. to IMaxCh4
EnDeadBandCh5
Disabled
Enabled
-
-
Disabled
Enable amplitude deadband reporting for
channel 5
DeadBandCh5
0.00 - 20.00
mA
0.01
1.00
Deadband amplitude for channel 5
IMinCh5
-25.00 - 25.00
mA
0.01
4.00
Min current of transducer for Channel 5
IMaxCh5
-25.00 - 25.00
mA
0.01
20.00
Max current of transducer for Channel 5
ValueMinCh5
-10000000000.000
-
10000000000.000
-
0.001
4.000
Min primary value corr. to IMinCh5
ValueMaxCh5
-10000000000.000
-
10000000000.000
-
0.001
20.000
Max primary value corr. to IMaxCh5
EnDeadBandCh6
Disabled
Enabled
-
-
Disabled
Enable amplitude deadband reporting for
channel 6
DeadBandCh6
0.00 - 20.00
mA
0.01
1.00
Deadband amplitude for channel 6
IMinCh6
-25.00 - 25.00
mA
0.01
4.00
Min current of transducer for Channel 6
Table continues on next page
1MRK 511 408-UUS A
Section 23
IED hardware
Phasor measurement unit RES670 2.2 ANSI
843
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...