PUREV
0.6 * INDirPU
PUFW
-RCA -85 deg
40% of
INDirPU
INDirPU
RCA
65°
VPol = -3V
0
I = 3I
op 0
RCA +85 deg
RCA -85 deg
Characteristic
for PUREV
Characteristic
for PUFW
Characteristic for reverse
release of measuring steps
Characteristic for forward
release of measuring steps
-RCA +85 deg
ANSI11000243-1-en.ai
Operating area
Operating area
ANSI11000243 V1 EN-US
Figure 60:
Operating characteristic for ground-fault directional element using the
zero sequence components
The relevant setting parameters for the directional supervision element are:
•
The directional element will be internally enabled to trip as soon as Iop is bigger
than 40% of
IDirPU
and the directional condition is fulfilled in the set direction.
•
The relay characteristic angle
AngleRCA
, which defines the position of forward
and reverse areas in the operating characteristic.
The directional comparison will set the output binary signals:
1. PUFW=1 when operating quantity magnitude Iop x cos(φ -
AngleRCA
) is bigger
than setting parameter
IDirPU
and directional supervision element detects fault in
forward direction.
2. PUREV=1 when operating quantity magnitude Iop x cos(φ -
AngleRCA
) is bigger
than 60% of setting parameter
IDirPU
and directional supervision element detects
fault in reverse direction.
Section 8
1MRK 511 408-UUS A
Current protection
206
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...