Name
Values (Range)
Unit
Step
Default
Description
IAngComp5
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 5% of In
IAngComp30
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 30% of In
IAngComp100
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 100% of In
IA_LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range, common for
all limits
IB_ZeroDb
0 - 100000
m%
500
1000
Magnitude zero point clamping in 0,001% of
range
IB_HiHiLim
0.0 - 500.0
%IB
0.1
150.0
High High limit in % of IBase
IB_HiLim
0.0 - 500.0
%IB
0.1
120.0
High limit in % of IBase
IB_LowLim
0.0 - 500.0
%IB
0.1
80.0
Low limit in % of IBase
IB_LowLowLim
0.0 - 500.0
%IB
0.1
60.0
Low Low limit in % of IBase
IB_LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range, common for
all limits
IC_ZeroDb
0 - 100000
m%
500
1000
Magnitude zero point clamping in 0,001% of
range
IC_HiHiLim
0.0 - 500.0
%IB
0.1
150.0
High High limit in % of IBase
IC_HiLim
0.0 - 500.0
%IB
0.1
120.0
High limit in % of IBase
IC_LowLim
0.0 - 500.0
%IB
0.1
80.0
Low limit in % of IBase
IC_LowLowLim
0.0 - 500.0
%IB
0.1
60.0
Low Low limit in % of IBase
IC_LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range, common for
all limits
PID-6738-SETTINGS v2
Table 379:
VMMXU Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
VAB_DbRepInt
1 - 100000
Type
1
10
Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
Operation
Disabled
Enabled
-
-
Disabled
Disbled/Enabled operation
VAB_ZeroDb
0 - 100000
m%
500
1000
Magnitude zero point clamping in 0,001% of
range
VAB_Min
0.0 - 200.0
%VB
0.1
50.0
Minimum value in % of VBase
VAB_Max
0.0 - 200.0
%VB
0.1
200.0
Maximum value in % of VBase
VAB_RepTyp
Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
-
-
Cyclic
Reporting type
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
Table continues on next page
1MRK 511 408-UUS A
Section 16
Monitoring
Phasor measurement unit RES670 2.2 ANSI
501
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...