tOpen
t1
t2
t3
tClose
t4
Main Contact
POSCLOSE
POSOPEN
0
1
0
1
1
0
tTravelOpen = tOpen + t1 + t2
tTravelClose = t3 + t4
IEC12000616_2_en.vsd
IEC12000616 V2 EN-US
Figure 209:
Travel time calculation
There is a time difference t1 between the pickup of the main contact opening and the
opening of the
POSCLOSE
auxiliary contact. Similarly, there is a time difference t2
between the time when the
POSOPEN
auxiliary contact opens and the main contact is
completely open. Therefore, a correction factor needs to be added to get the actual
opening time. This factor is added with the
OpenTimeCorr
(t1+t2) setting. The closing
time is calculated by adding the value set with the
CloseTimeCorr
(t3+t4) setting to the
measured closing time.
The last measured opening travel time (
TTRVOP
) and the closing travel time
(
TTRVCL
) are given as service values.
The values can be reset using the Clear menu on the LHMI or by activation the input
RSTCBWR
.
Alarm limit check
When the measured opening travel time is longer than the value set in the
tTrOpenAlm
setting, the
TRVTOPAL
output is activated. Similarly, when the measured closing
travel time is longer than the value set in the
tTrCloseAlm
setting, the
TRVTCLAL
output is activated.
It is also possible to block the
TRVTCLAL
and
TRVTOPAL
alarm signals by activating
the
BLKALM
input.
1MRK 511 408-UUS A
Section 16
Monitoring
Phasor measurement unit RES670 2.2 ANSI
539
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...