Name
Values (Range)
Unit
Step
Default
Description
IAngComp5
-10.000 - 10.000
Deg
0.001
0.000
Corr of error betw current and voltage angles
at 5% of Ir
IAngComp30
-10.000 - 10.000
Deg
0.001
0.000
Corr of error betw current and voltage angles
at 30% of Ir
IAngComp100
-10.000 - 10.000
Deg
0.001
0.000
Corr of error betw current and voltage angles
at 100% of Ir
Table 144:
GOPPDOP (32) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
Mode
A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
-
-
Pos Seq
Selection of measured current and voltage
8.7.6
Monitored data
PID-3710-MONITOREDDATA v6
Table 145:
GOPPDOP (32) Monitored data
Name
Type
Values (Range)
Unit
Description
P
REAL
-
MW
Active power P in MW
PPERCENT
REAL
-
%
Active power P in % of SBase
Q
REAL
-
MVAr
Reactive power Q in MVAr
QPERCENT
REAL
-
%
Reactive power Q in % of
SBase
8.7.7
Operation principle
SEMOD172154-4 v3
A simplified scheme showing the principle of the power protection function is shown
in figure
. The function has two stages with individual settings.
Section 8
1MRK 511 408-UUS A
Current protection
264
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...