Table 186:
CVGAPC Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
MultPU_OC1
1.0 - 10.0
-
0.1
2.0
Multiplier for scaling the current setting value
for OC1
ResCrvType_OC1
Instantaneous
IEC Reset
ANSI reset
-
-
Instantaneous
Selection of reset curve type for OC1
tResetDef_OC1
0.00 - 6000.00
s
0.01
0.00
Reset time delay used in IEC Definite Time
curve OC1
P_OC1
0.001 - 10.000
-
0.001
0.020
Parameter P for customer programmable
curve for OC1
A_OC1
0.000 - 999.000
-
0.001
0.140
Parameter A for customer programmable
curve for OC1
B_OC1
0.000 - 99.000
-
0.001
0.000
Parameter B for customer programmable
curve for OC1
C_OC1
0.000 - 1.000
-
0.001
1.000
Parameter C for customer programmable
curve for OC1
PR_OC1
0.005 - 3.000
-
0.001
0.500
Parameter PR for customer programmable
curve for OC1
TR_OC1
0.005 - 600.000
-
0.001
13.500
Parameter TR for customer programmable
curve for OC1
CR_OC1
0.1 - 10.0
-
0.1
1.0
Parameter CR for customer programmable
curve for OC1
MultPU_OC2
1.0 - 10.0
-
0.1
2.0
Multiplier for scaling the current setting value
for OC2
ResCrvType_OC2
Instantaneous
IEC Reset
ANSI reset
-
-
Instantaneous
Selection of reset curve type for OC2
tResetDef_OC2
0.00 - 6000.00
s
0.01
0.00
Reset time delay used in IEC Definite Time
curve OC2
P_OC2
0.001 - 10.000
-
0.001
0.020
Parameter P for customer programmable
curve for OC2
A_OC2
0.000 - 999.000
-
0.001
0.140
Parameter A for customer programmable
curve for OC2
B_OC2
0.000 - 99.000
-
0.001
0.000
Parameter B for customer programmable
curve for OC2
C_OC2
0.000 - 1.000
-
0.001
1.000
Parameter C for customer programmable
curve for OC2
PR_OC2
0.005 - 3.000
-
0.001
0.500
Parameter PR for customer programmable
curve for OC2
TR_OC2
0.005 - 600.000
-
0.001
13.500
Parameter TR for customer programmable
curve for OC2
CR_OC2
0.1 - 10.0
-
0.1
1.0
Parameter CR for customer programmable
curve for OC2
tResetDef_UC2
0.00 - 6000.00
s
0.01
0.00
Reset time delay used in IEC Definite Time
curve UC2
Table continues on next page
1MRK 511 408-UUS A
Section 11
Multipurpose protection
Phasor measurement unit RES670 2.2 ANSI
333
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...