![ABB Relion RES670 Technical Manual Download Page 711](http://html.mh-extra.com/html/abb/relion-res670/relion-res670_technical-manual_4485711.webp)
19.7.13.5
Settings
PID-3970-SETTINGS v5
Table 532:
I103GENCMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
PulseLength
0.000 - 60.000
s
0.001
0.400
Pulse length
InfNo
1 - 255
-
1
1
Information number for command output
(1-255)
19.7.14
IED commands with position and select for IEC 60870-5-103
I103POSCMD
19.7.14.1
Functionality
GUID-1E40B94D-B6A6-42F0-8757-A47B8A3FA3CD v7
I103POSCMD is a transceiver function that monitors activity on its input signals and
interprets any state transition into commands then sent over an established IEC
60870-5-103 link. Additionally, it listens for general interrogation (GI) requests and
replies to those with a GI response message with the current state of each connected
input.
Input POSITION is a double-indication signal, and it is GI enabled. This means that
any state transition, that is to ON, OFF, intermediate and faulty, is reported
spontaneously. However, the intermediate and faulty states may be suppressed by
setting the
Report Intermediate Position
=
Off
. See the settings for RS485 and optical
serial communication for more information.
Input SELECT is a single-indication signal, and it is also GI enabled. State transitions
to ON and OFF are reported spontaneously.
When input BLOCK is ON, the function will ignore GI requests and cease all
monitoring activity. Consequently, no transitions will be detected.
The I103POSCMD function is also equipped with two additional commands: Operate
and Cancel. These are hidden in ACT and respond only to base INF +2 and +3
respectively. The base INF (Information Number) parameter is an IEC 60870-5-103
identifier that associates a function in a 103 Master (such as Scada) with its equivalent
in the IED.
1MRK 511 408-UUS A
Section 19
Station communication
Phasor measurement unit RES670 2.2 ANSI
705
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...