Figure 229:
BINSTATREP logical diagram
16.8
Measured value expander block RANGE_XP
SEMOD52451-1 v2
16.8.1
Identification
SEMOD113212-2 v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Measured value expander block
RANGE_XP
-
-
16.8.2
Functionality
SEMOD52450-4 v7
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU
and VNMMXU), current and voltage sequence measurement functions (CMSQI and
VMSQI) and IEC 61850 generic communication I/O functions (MVGAPC) are
provided with measurement supervision functionality. All measured values can be
supervised with four settable limits: low-low limit, low limit, high limit and high-high
limit. The measure value expander block (RANGE_XP) has been introduced to enable
translating the integer output signal from the measuring functions to 5 binary signals:
below low-low limit, below low limit, normal, above high limit or above high-high
limit. The output signals can be used as conditions in the configurable logic or for
alarming purpose.
1MRK 511 408-UUS A
Section 16
Monitoring
Phasor measurement unit RES670 2.2 ANSI
583
Technical manual