The PMU clients receiving the UDP frames can also connect to the IED to request
(command frame) config frame 1, config frame 2, config frame 3, or header frame, and
to disable/enable real time data. This can be done by connecting to the TCP port
selected in
TCPportUDPdataCtrl[x]
for each UDP group. This connection is done
using TCP. The IED allows 4 concurrent client connections for every
TCPportUDPdataCtrl[x]
port (for each UDP client group[x]).
If the client tries to connect on
TCPportUDPdataCtrl[x
] port using a PMU-ID other
than what is configured for that PMUREPORT instance (
PMUReportUDP[x]
), then
that client is immediately disconnected and the
UDPCtrlCfgErrCnt
is incremented in
PMU Diagnostics on LHMI at
Main menu/Diagnostics/Communication/PMU
diagnostics/PMUSTATUS:1
Even if the parameter
SendDataUDP[x]
is set to
Disable
it is still possible for the
clients to connect on the TCP port and request the configuration frames.
6.1.4
Settings
SEMOD119927-1 v2
PID-6710-SETTINGS v4
Table 44:
PMUCONF Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
1344TCPport
1024 - 65534
-
1
4711
TCP port for control of IEEE 1344 data for
TCP clients
C37.118TCPport
1024 - 65534
-
1
4712
TCP port for control of IEEE C37.118 data for
TCP clients
TCPportUDPdataCtrl1
1024 - 65534
-
1
4713
TCP port for control of data sent over UDP
client group1
SendDataUDP1
Disabled
Enabled
SetByProtocol
-
-
Disabled
Send data to UDP client group1
ProtocolOnUDP1
IEEE1344
C37.118
-
-
C37.118
Select protocol for UDP client group1
PMUReportUDP1
1 - 2
-
1
1
PMUREPORT instance used for UDP client
group1
UDPDestAddres1
0 - 16
IP
Address
1
234.5.6.7
UDP destination address for UDP client
group1
UDPDestPort1
1024 - 65534
-
1
8910
UDP destination port for UDP client group1
SendCfgOnUDP1
Disabled
On
-
-
Disabled
Send Config frame2 on UDP for group1
TCPportUDPdataCtrl2
1024 - 65534
-
1
4714
TCP port for control of data sent over UDP
client group2
SendDataUDP2
Disabled
Enabled
SetByProtocol
-
-
Disabled
Send data to UDP client group2
Table continues on next page
Section 6
1MRK 511 408-UUS A
Wide area measurement system
108
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...