8.1.5
Settings
PID-6973-SETTINGS v3
Table 93:
OC4PTOC (51_67) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
AngleRCA
40 - 65
Deg
1
55
Relay characteristic angle (RCA)
AngleROA
40 - 89
Deg
1
80
Relay operation angle (ROA)
NumPhSel
1 out of 3
2 out of 3
3 out of 3
-
-
1 out of 3
Number of phases required for phase
selection (1 of 3, 2 of 3, 3 of 3)
DirModeSel1
Disabled
Non-directional
Forward
Reverse
-
-
Non-directional
Directional mode of step 1 (Disabled, Nondir,
Forward, Reverse)
Characterist1
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
-
-
ANSI Def. Time
Selection of time delay curve type for step 1
Pickup1
5 - 2500
%IB
1
1000
Operating phase current level for step 1 in %
of IBase
t1
0.000 - 60.000
s
0.001
0.000
Def time delay or add time delay for inverse
char of step 1
TD1
0.05 - 999.00
-
0.01
0.05
Time dial multiplier for the inverse time delay
for step 1
IMin1
1 - 10000
%IB
1
100
Minimum operate current for step1 in % of
IBase
t1Min
0.000 - 60.000
s
0.001
0.000
Minimum operate time for inverse curves for
step 1
MultPU1
1.0 - 10.0
-
0.1
2.0
Multiplier for current operate level for step 1
DirModeSel2
Disabled
Non-directional
Forward
Reverse
-
-
Non-directional
Directional mode of step 2 (Disabled, Nondir,
Forward, Reverse)
Table continues on next page
1MRK 511 408-UUS A
Section 8
Current protection
Phasor measurement unit RES670 2.2 ANSI
173
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...