21.4.5
Settings
GUID-ECE18AA9-15CC-4522-AA31-78C4F0F052E4 v3
The function does not have any parameters available in Local HMI or in Protection and
Control IED Manager (PCM600)
21.4.6
Operation principle
SEMOD158543-4 v5
Authority status (ATHSTAT) function informs about two events related to the IED and
the user authorization:
•
the fact that at least one user has tried to log on wrongly into the IED and it was
blocked (the output USRBLKED)
•
the fact that at least one user is logged on (the output LOGGEDON)
Whenever one of the two events occurs, the corresponding output (USRBLKED or
LOGGEDON) is activated. The output can for example, be connected on Event
(EVENT) function block for LON/SPA.The signals are also available on IEC 61850
station bus.
21.5
Self supervision with internal event list INTERRSIG
IP1721-1 v2
21.5.1
Functionality
M11399-3 v7
Self supervision with internal event list function listens and reacts to internal system
events, generated by the different built-in self-supervision elements. The internal
events are saved in an internal event list presented on the LHMI and in PCM600 event
viewer tool.
21.5.2
Function block
M11402-3 v6
INTERRSIG
FAIL
WARNING
TSYN CERR
RTCERR
STUPBLK
IEC09000787-2-en.vsdx
IEC09000787 V2 EN-US
Figure 289:
INTERRSIG function block
Section 21
1MRK 511 408-UUS A
Security
752
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...