Description
Value
Dynamic withstand
250 × I
r
one half wave
Burden
< 20 mVA at I
r
= 1 A
< 150 mVA at I
r
= 5 A
*) max. 350 A for 1 s when COMBITEST test switch is included.
Voltage inputs **)
Rated voltage U
r
110 or 220 V
Operating range
0 - 340 V
Thermal withstand
450 V for 10 s
420 V continuously
Burden
< 20 mVA at 110 V
< 80 mVA at 220 V
**) all values for individual voltage inputs
Note! All current and voltage data are specified as RMS values at rated frequency
Table 635:
TRM - Energizing quantities, rated values and limits for measuring transformer
Description
Value
Frequency
Rated frequency f
r
50/60 Hz
Operating range
f
r
± 10%
Current inputs
Rated current I
r
1A
5 A
Operating range
(0-1.8) × I
r
(0-1.6) × I
r
Thermal withstand
80 × I
r
for 1 s
25 × I
r
for 10 s
10 × I
r
for 1 min
1.8 × I
r
for 30 min
1.1 × I
r
continuously
65 × I
r
for 1 s
20 × I
r
for 10 s
8 × I
r
for 1 min
1.6 × I
r
for 30 min
1.1 × I
r
continuously
Burden
< 200 mVA at I
r
< 350 mVA at I
r
Voltage inputs *)
Rated voltage U
r
110 or 220 V
Operating range
0 - 340 V
Thermal withstand
450 V for 10 s
420 V continuously
Burden
< 20 mVA at 110 V
< 80 mVA at 220 V
*) all values for individual voltage inputs
Note! All current and voltage data are specified as RMS values at rated frequency
Section 23
1MRK 511 408-UUS A
IED hardware
810
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...