Name
Values (Range)
Unit
Step
Default
Description
RatedOperCurr
100.00 - 5000.00
A
0.01
1000.00
Rated operating current of the breaker
OperNoRated
1 - 99999
-
1
10000
Number of operations possible at rated
current
RatedFltCurr
500.00 - 99999.99
A
0.01
5000.00
Rated fault current of the breaker
OperNoFault
1 - 10000
-
1
1000
Number of operations possible at rated fault
current
tTrOpenAlm
0.000 - 0.200
s
0.001
0.040
Alarm level for open travel time
tTrCloseAlm
0.000 - 0.200
s
0.001
0.040
Alarm level for close travel time
OperAlmLevel
0 - 9999
-
1
200
Alarm level for number of operations
OperLOLevel
0 - 9999
-
1
300
Lockout level for number of operations
AccSelCal
Aux Contact
Trip Signal
-
-
Trip Signal
Accumulated energy calculation selection
CurrExponent
0.50 - 3.00
-
0.01
2.00
Current exponent value used for energy
calculation
AccStopCurr
5.00 - 100.00
%IB
0.01
10.00
RMS current level below which energy
accumulation stops
AlmAccCurrPwr
0.00 - 20000.00
-
0.01
2500.00
Alarm level for accumulated I^CurrExponent
integrated over CB open travel time
LOAccCurrPwr
0.00 - 20000.00
-
0.01
2500.00
Lockout level for accumulated
I^CurrExponent integrated over CB open
travel time
SpChAlmTime
0.00 - 60.00
s
0.01
1.00
Alarm level for spring charging time
InitCBRemLife
1 - 99999
-
1
10000
Initial value for remaining life estimates
InactiveAlDays
0 - 9999
Day
1
2000
Alarm level for inactive days counter
Table 412:
SSCBR Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
OpenTimeCorr
-0.100 - 0.100
s
0.001
0.010
Correction for open travel time
CloseTimeCorr
-0.100 - 0.100
s
0.001
0.010
Correction for close travel time
DirCoef
-3.00 - -0.50
-
0.01
-1.50
Directional coefficient for CB life calculation
CBLifeAlmLevel
1 - 99999
-
1
5000
Alarm level for CB remaining life
ContTrCorr
-0.010 - 0.010
s
0.001
0.005
Correction for time difference in auxiliary and
main contacts open time
OperTimeDelay
0.000 - 0.200
s
0.001
0.020
Time delay between change of status of trip
output and start of main contact separation
tDGasPresAlm
0.00 - 60.00
s
0.01
0.10
Time delay for gas pressure alarm
tDGasPresLO
0.00 - 60.00
s
0.01
0.10
Time delay for gas pressure lockout
InitCounterVal
0 - 9999
-
1
0
Initial value for number of operations
Table continues on next page
1MRK 511 408-UUS A
Section 16
Monitoring
Phasor measurement unit RES670 2.2 ANSI
535
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...