72
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
Setting Value
Function
Description
Ref.
25
PI2 Control Setpoint
Enters the PI2 Control setpoint level as a percentage of the
S3-02 [PI2 Control Transducer Scale]
value.
Note:
Parameters
S3-03 [PI2 Control Decimal Place Pos]
and
S3-04 [PI2 Control Unit Selection]
set the resolution and
unit.
26
PI2 Control Feedback
Enters the PI2 Control feedback level as a percentage of the
S3-02 [PI2 Control Transducer Scale]
value.
Note:
Parameters
S3-03 [PI2 Control Decimal Place Pos]
and
S3-04 [PI2 Control Unit Selection]
set the resolution and
unit.
27
PI Auxiliary Control
Feedback
Enters the PI Auxiliary Control feedback value when
YF-01 = 1 [PI Aux Control Selection = Enabled]
.
Note:
•
The full-scale of the analog signal goes from 0% to
YF-02 [PI Aux Control Transducer Scale]
.
•
Parameter
YF-22 [PI Aux Level Decimal Place Pos]
sets the resolution.
2B
Emergency Override PID
Feedback
This input is the PID Feedback source when Emergency Override is running in PID mode (
S6-02 = 2 or 3 [Emergency
Override Ref Selection = System PID Mode or Independent PID Mode]
).
Note:
•
When
S6-02 = 2 [Emergency Override Ref Selection = System PID Mode]
, the full-scale of the analog signal
goes from
b5-71 [Min PID Transducer Scaling]
to
b5-38 [PID User Unit Display Scaling]
.
•
When
S6-02 = 3 [Independent PID Mode]
, the full-scale of the analog signal goes from
b5-71
to
S6-03 [EMOVR
Independent PID Scale]
.
•
When you set MEMOBUS register 3A93h bit 4, register 3A95h becomes the Emergency Override Feedback
source.
2C
Emergency Override PID
Setpoint
This input is the PID Setpoint source when Emergency Override is running in PID mode (
S6-02 = 2 or 3 [Emergency
Override Ref Selection = System PID Mode or Independent PID Mode]
).
Note:
•
When
S6-02 = 2 [Emergency Override Ref Selection = System PID Mode]
, the full-scale of the analog signal
goes from
b5-71 [Min PID Transducer Scaling]
to
b5-38 [PID User Unit Display Scaling]
.
•
When
S6-02 = 3 [Independent PID Mode]
, the full-scale of the analog signal goes from
b5-71
to
S6-03 [EMOVR
Independent PID Scale]
.
•
When you set MEMOBUS register 3A93h bit 5, register 3A96h becomes the Emergency Override Setpoint
source.
2D
Differential Level Source
Enters a feedback value to calculate the Differential Level between the
Differential Level Source
feedback and the
primary
PID Feedback [H3-xx = B]
.
Note:
The full-scale of the analog signal goes from
b5-71 [Min PID Transducer Scaling]
to
b5-38 [PID User Unit
Display Scaling]
.
2E
HAND Frequency Ref or
Setpoint
Enters the
S5-05 [HAND Frequency Reference]
value or the
S5-06 [HAND Setpoint]
value. When
S5-01 = 0 [HAND
Frequency Reference Source = HAND Analog Input]
and
S5-03 = 0 [HAND Mode PI Selection = Disabled]
, the drive
enters HAND Frequency Reference. When
b5-01 ≠ 0
,
S5-01 = 0
, and
S5-03 = 1 [Enabled]
, the drive enters HAND
Setpoint.
Note:
•
When PID is enabled, the full-scale of the analog signal goes from
b5-71 [Min PID Transducer Scaling]
to
b5-38
[PID User Unit Display Scaling]
.
•
When PID is disabled, the drive enters this analog signal as the percentage of the
E1-04 [Maximum Output
Frequency]
value.
30
DWEZ Analog Input 1
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
31
DWEZ Analog Input 2
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
◆
H4: Analog Outputs
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
H4-01
(041D)
Terminal FM Analog
Output Select
Sets the monitor number to send from MFAO terminal FM.
Set the
x-xx
part of the
Ux-xx [Monitor]
. For example, set
H4-01 = 102
to monitor
U1-02
[Output Frequency]
.
102
(000 - 999)
H4-02
(041E)
RUN
Terminal FM Analog
Output Gain
Sets the gain of the monitor signal that is sent from MFAO terminal FM.
Sets the analog signal output level from the terminal FM at 10 V or 20 mA as 100% when
an output for monitoring items is 100%.
100.0%
(-999.9 - +999.9%)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...