YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
485
Table 2.82 Apply Parameter Changes to Prompt when Y9-98 = 1
Status
Keypad Display
Description
A System-Wide Parameter Is
Changed
When you change System-wide parameter, the keypad will show
[Apply Changes to]
message and
you can set one of these selections:
•
[All Devices on Memobus Network]
: Writes the changes to the drive on which you changed the
parameter and all other online drives.
•
[This Device Only]
: Writes the changes only to the drive on which you changed the parameter.
•
[Cancel]
: Cancels the change.
Writing to Nodes Is in Progress
When you set
[All Devices on Memobus Network]
, the MEMOBUS Multiplex network will start to
write each node. The keypad shows the
[WAIT Network Write in Progress]
message for 5 seconds
while the MEMOBUS Multiplex network writes to each node.
All Drives Have Been Accessed to
Update the Nodes
After all drives have been accessed, the keypad will show
[Node Addresses Updated]
message. The
number of nodes as specified by
Y9-25 [Highest Node Address]
.
On the keypad:
•
[x]
shows nodes that did not update
•
[o]
shows nodes that completed successfully
When all nodes are updated successfully, the keypad will show the
[Node Addresses Updated]
message for 1.5 seconds or until you push a key.
If there are nodes that did not update, the keypad will show the message for 15 seconds or until you
push a key. The keypad then goes back to the parameter selection screen.
Taking Longer Than 5 Seconds to
Confirm the Parameter Change
If the drive on the network does not receive confirmations from all nodes for longer than 5 seconds,
the keypad will show a Waiting on Confirmation message.
The Waiting on Confirmation message will go away after 15 seconds or when you push a key. The
display then goes back to the parameter selection screen.
When the drive receives confirmation before 15-second timer is expired, the keypad will show the
[Node Addresses Updated]
message.
■
Y9-01: Lead Drive Selection
No.
(Hex.)
Name
Description
Default
(Range)
Y9-01
(3DF4)
Lead Drive Selection
Sets how to select the new Lead Drive.
1
(0 - 2)
Note:
•
When
Y9-01 = 1
, MEMOBUS network uses monitor
U4-01 [Cumulative Ope Time]
. The settings of
o4-01 [Elapsed Operating Time
Setting]
and
o4-02 [Elapsed Operating Time Selection]
will have a direct effect on this parameter.
Yaskawa recommends to keep
o4-02 = 1 [U4-01 Shows Total RUN Time]
.
•
When
U4-01
> 65535 hours, alternation timer has reached its maximum value.
Yaskawa recommends to reset the runtime hours (
o4-01
) on all the drives to keep the function working correctly.
0 : Next Available
1 : Lowest Runtime
2 : Stop History
■
Y9-02: System Feedback Source
No.
(Hex.)
Name
Description
Default
(Range)
Y9-02
(3DF5)
System Feedback Source
Sets the signal to use for PID Feedback when
Y1-01 = 3 [Multiplex Mode = Memobus Network]
.
0
(0 - 3)
0 : Analog Only
The drive will not read the Network PID Feedback register as the feedback source, although the drive will continue to
transmit its own PID Feedback signal to the network.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...