2.2 A: Initialization Parameters
174
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
User Parameter No.
Parameter No. Saved
Name
A2-21
Y1-09
Low Feedback Lvl Fault Dly Time
A2-22
Y2-01
Sleep Level Type
A2-23
Y2-02
Sleep Level
A2-24
Y2-03
Sleep Delay Time
A2-25
Y2-04
Sleep Activation Level
8 : Pump Network Multiplex
The drive automatically sets the parameters in
for a pump network multiplex application.
Table 2.18 Optimal Settings for Pump Network Multiplex Applications
No.
Name
Optimal Value
A1-02
Control Method Selection
0: V/f Control
b1-01
Frequency Reference Selection 1
0: Keypad
b1-02
Run Command Selection 1
0: Keypad
b5-01
PID Mode Setting
1: Standard
b5-39
PID User Unit Display Digits
1: One Decimal Places (XXXX.X)
b5-46
PID Unit Display Selection
1: PSI (pounds per square inch)
C1-01
Acceleration Time 1
20.0 s
C1-02
Deceleration Time 1
20.0 s
H2-02
Term M3-M4 Function Selection
42: Pressure Reached
H2-03
Term M5-M6 Function Selection
37: During Frequency Output
H3-09
Terminal A2 Signal Level Select
2: 4 to 20 mA
H3-10
Terminal A2 Function Selection
B: PID Feedback
L5-01
Number of Auto-Restart Attempts
5
L5-49
Fault Retry Speed Search Select
0: Disabled
S5-05
HAND Frequency Reference
40.00 Hz
S5-10
AUTO Key Memory at Power Down
1: Enabled w/ Memory
Y1-01
Multiplex Mode
3: Memobus Network
Y1-04
Sleep Wake-up Level
-10.0
Y1-06
Minimum Speed
40.0
Y1-11
High Feedback Level
100.0
Y2-01
Sleep Level Type
0: Output Frequency
Y2-23
Anti-No-Flow Bandwidth
0.40%
Y4-12
Thrust Frequency
30.0 Hz
Y4-17
Utility Start Delay
0.2 min
Y9-06
Lag Fixed Speed
54.0 Hz
YA-01
Setpoint 1
80.0%
The drive saves the parameters in
as user parameters.
Table 2.19 Parameters Saved as User Parameters with the Pump Network Multiplex Preset
User Parameter No.
Parameter No. Saved
Name
A2-01
b1-03
Stopping Method Selection
A2-02
b1-04
Reverse Operation Selection
A2-03
b2-09
Pre-heat Current 2
A2-04
b5-01
PID Mode Setting
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...