TOEPYAIHV6002A HV600 Drive Programming
53
Setting Value
Function
Description
Ref.
C
Analog Terminal Enable
Selection
Sets the command that enables or disables the terminals selected in
H3-14 [Analog Input Terminal Enable Sel]
.
ON : Input to the terminal selected with
H3-14
is enabled
OFF : Input to the terminal selected with
H3-14
is disabled
E
ASR Integral Reset
Sets the command to reset the integral value and use PI control or P control for the speed control loop.
ON : P control
OFF : PI control
F
Not Used
Use this setting for unused terminals or to use terminals in through mode.
10
Up Command
Sets the command to use a push button switch to increase the drive frequency reference. You must also set
Setting 11
[Down Command]
.
ON : Increases the frequency reference.
OFF : Holds the current frequency reference.
11
Down Command
Sets the command to use a push button switch to decrease the drive frequency reference. You must also set
Setting 10
[Up Command]
.
ON : Decreases the frequency reference.
OFF : Holds the current frequency reference.
12
Forward Jog
Sets the command to operate the motor in the forward direction at the Jog Frequency set in
d1-17 [Jog Reference]
.
13
Reverse Jog
Sets the command to operate the motor in the reverse direction at the Jog Frequency set in
d1-17 [Jog Reference]
.
14
Fault Reset
Sets the command to reset the current fault when the Run command is inactive.
Note:
The drive ignores the fault reset command when the Run command is active. Remove the Run command before
trying to reset a fault.
15
Fast Stop (N.O.)
Sets the command to ramp to stop in the deceleration time set in
C1-09 [Fast Stop Time]
when the input terminal is
activated while the drive is operating.
16
Motor 2 Selection
Sets the command for the drive to operate motor 1 or motor 2. Stop the motors before switching.
ON : Selects motor 2.
OFF : Selects motor 1.
17
Fast Stop (N.C.)
Sets the command to ramp to stop in the deceleration time set in
C1-09 [Fast Stop Time]
when the input terminal is
activated while the drive is operating.
18
Timer Function
Sets the command to start the timer function. Use this setting with
Timer Output [H2-xx = 12]
.
19
PID Disable
Sets the command to disable PID control when
b5-01 = 1 or 3 [PID Mode Setting = Standard or Fref + PID Trim]
.
ON : PID control disabled
OFF : PID control enabled
1B
Programming Lockout
Sets the command to prevent parameter changes when the terminal is OFF.
ON : Programming Lockout
OFF : Parameter Write Prohibit
1E
Reference Sample Hold
Sets the command to sample the frequency reference at terminals A1 or A2 and hold the frequency reference at that
frequency.
20
External Fault (NO-
Always-Ramp)
When the terminal activates, the drive ramps to stop in the selected deceleration time. Fault relay output terminal MA-
MC will turn ON, and MB-MC will turn OFF. The drive always detects external faults whether the drive is stopped or
running.
21
External Fault (NC-
Always-Ramp)
When the terminal deactivates, the drive ramps to stop in the selected deceleration time. Fault relay output terminal
MA-MC will turn ON, and MB-MC will turn OFF. The drive always detects external faults whether the drive is
stopped or running.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...